4.0 OPERATING MODE

If the thermostat activates heating, cooling, or constant fan operation, the numeric display will read ON.  Otherwise, 

the display will read FAN OFF and will indicate the time remaining until the fan is activated again. Once activated, the 

display will read FAN ON and the time remaining for FAN ON time.

The model FR-V has additional settings for outside air damper cycling. When the fan turns on, the damper will open and 

the display will read VENT ON and indicate the time remaining until the damper closes. Once the VENT ON time has ex

-

pired, the damper will close and the display will read VENT OFF and indicate the time remaining until the damper opens 

again. This cycle continues for as long as the fan is running. The vent will be closed any time the fan is not running and 

VENT ON and VENT OFF times will be reset to programmed values.

4.1 POWERING OFF

Warning: It is not recommended to turn off the AirCycler® if the unit is used as a ventilation controller.  The AirCycler® 

can be turned off during extended vacation periods or when the windows are open. It is very important to turn the Air

-

Cycler® back on after those periods. 

1.  In normal Operating Mode: Press and hold the Mode Key for six seconds to turn off the AirCycler®. All thermostat 

functions will continue to operate normally.

2.  To turn the AirCycler® back on, press the Mode Key.

4.2 TESTING

The Test Mode will display fan activity in seconds rather than minutes.  To activate Test Mode, follow these steps:

1.  Press the Mode Key once and then press it again and hold for six seconds. The display will indicate TEST.

2.  Exit Test Mode and return to Operating Mode by turning the AirCycler® off.

3.  Hold the Mode Key for six seconds, and then press Mode again to turn on the AirCycler®.

NOTE: 

As a safeguard, the AirCycler® will automatically exit Test mode after ten minutes.

Summary of Contents for FRV

Page 1: ...Ventilation Products AirCycler FRV Installation User s Guide VENTILATION MADE BREEZY a breeze to install a breeze to use ...

Page 2: ...er the existing HVAC system can be used to provide venti lation The AirCycler enables this ventilation system to work properly The AirCycler FRV adds an output to operate a motorized outside damper that limits excessive ventilation Motorized Damper sold separately see AirCycler VS ACVS 06 for more information IMPORTANT If the AirCycler was installed in your home as a ventilation controller DO NOT ...

Page 3: ... C W Y from the air handler to the thermostat can run parallel with the wiring from the AirCycler to the air handler The fan wire G needs to be interrupted by the AirCycler Some thermostats do not require a C connection The AirCycler requires a C for power which must be wired to the furnace KEY Y Cooling R 24 VAC Power W Heating Gt Fan to Thermostat Gf Fan to Furnace C Common V Vent Air Handler Ai...

Page 4: ...ole in mounting base 5 Adjust length and routing of each wire to reach proper terminal and connector block on mounting base with 1 4 in of extra wire Strip only 1 4 in of insulation from each wire to prevent adjacent wires from shorting together when connected 6 Connect wires to proper terminals of the con nector block Figure 3 Both R and C must be connected for proper operation 7 Improper wiring ...

Page 5: ...rCycler This will also keep the AirCycler off even after power is lost The AirCycler retains settings even after power is lost NOTE In humid climates the FAN OFF time should be at least 6 minutes This allows moisture on the AC coil to dry preventing condensation in cold supply ducts 3 3 CONFIGURE VENT ON TIME 1 Press the Mode Key VENT ON will flash 2 Use the Increase or Decrease Keys to change the...

Page 6: ... and VENT OFF times will be reset to programmed values 4 1 POWERING OFF Warning It is not recommended to turn off the AirCycler if the unit is used as a ventilation controller The AirCycler can be turned off during extended vacation periods or when the windows are open It is very important to turn the Air Cycler back on after those periods 1 In normal Operating Mode Press and hold the Mode Key for...

Page 7: ...irmly seated in the base Problem AirCycler FR V turns furnace fan on and off but the motorized damper does not cycle Solution Check 1 Confirm that the AirCycler is providing a 24 VAC signal to the motorized damper 2 Verify that 24 VAC motorized damper is operational by powering directly with a 24 VAC signal 3 Check continuity in the wiring between the damper and the AirCycler Problem A C turns on ...

Reviews: