Table
A-9: BCL-S & BFL
AIRFLOW CHARACTERISTICS – DIRECT DRIVE
Furnace Model
Motor HP
Blower
ΔT
Motor FLA
Speed
CFM
External Static Pressure – Inches w
.c.
0.20
0.25
0.30
0.40
0.50
0.60
BCL-S2
BFL-2
1/2 HP
100-10R
85°F
7.0
High
1810
1775
1740
1675
1585
1510
Med-High
1570
1555
1540
1495
1445
1375
Med-Low
1090
1085
1080
1070
1065
1050
Low
710
700
700
690
665
650
BCL-ST2
BFL-T2
1 HP
120-1
1T
85°F
12.3
14.0 MAX
High
2188
2161
2133
2069
2016
1933
Medium
1742
1730
1718
1702
1670
1604
Low
1410
1410
1410
1390
1374
1326
TABLE
A
-1
0:
BCL
-S
&
BFL
AIRFLOW
CHARACTERISTICS
–
BEL
T
DRIVE
Furnace Model
Motor HP
Motor FLA
ΔT
Blower
Blower Pulley
Motor Pulley Turns Out
CFM
External Static Pressure – Inches w
.c.
0.20
0.25
0.30
0.40
0.50
0.60
BCL-S2
BFL-2
1/3 HP
5.4
85°F
100-10R
7 x ¾
0
1425
1355
1280
1125
905
516
2
1280
1200
1125
915
555
256
4
111
5
1020
905
530
225
11
6
920
800
645
190
- - -
- - -
BCL-S2
BFL-2
1/2 HP
7.8
85°F
100-10R
6 x ¾
0
1535
1475
1410
1250
1065
845
2
1440
1370
1295
1090
880
472
4
1320
1250
1170
970
625
319
6
1225
1140
1040
835
435
132