7
Installation height of ACGV models
Types
ACG26V
ACG36V
ACG55V
ACG75V
ACG95V
A
810
810
1 040
1 120
1 120
B
800
820
840
840
840
C
460
570
700
820
1075
D
134.5
134.5
134.5
149.5
149.5
E
380
490
610
730
——–
H
162
217
252
366
455
Ø F
80/125
130
130
130
Ø Air
130
130
130
Ø G (gas)
1/2
1/2
1/2
3/4
3/4
80/125
I
479
479
677
677
677
ACG28V
1040
790
460
120
380
164
677
80/125
1/2
ACG45V
1 040
820
570
128
490
217
677
100 / 100
1/2
The ACGV models are retained at their upper part by four tightened
M8 nuts.
Blowing is vertical towards the ground and the installation height
must not be lower or higher than that recommended.
To get the best performance from the
ACGV
gas destratificators, we
recommend you to respect the following heights.
ACG26V ACG36V ACG55V ACG75V ACG95V
L1 (min)
m
0,45
0,45
0,45
0,50
0,60
L2 (min)
m
1
1
1
1
1
L3 (min)
m
1
1
1
1
1
H : Height (mini/
max)
m
4 / 5
4 / 6
5 / 8
6 / 12
6 / 12
P : Max air reach
m
P = 16-
H
P = 20-
H
P = 25-
H
P = 28-
H
P = 30-
H
Types
Overall dimensions of the ACGV models
I
I