Ducting should be installed by a professional and should not provide greater than 100 Pascals resistance.
Flexible ducting should be avoided as it may cause excessive back-pressure on the fan, and lead to reduced
airflow.
Any other configuration is non-standard and should be discussed with the manufacturer.
Assembly of Accessories
These items apply only when they have been ordered with the AirBench.
FRONT DEFLECTOR
If a deflector skirt is supplied loose with the unit, the unit must be raised slightly to allow the skirt to be fitted.
A pack of fixing bolts is supplied with the skirt; threaded inserts are fitted to the base of the bench to allow
attachment of the deflector. To fit, position the deflector skirt, and use the bolts to fix to the base of the bench.
Where a front deflector is supplied, ensure air is allowed to exhaust from sides or rear to avoid
motor overload.
ENCLOSURE
Enclosures are supplied fully assembled where possible. Where shipping does not permit assembly prior to
dispatch, enclosures should be assembled as follows using bolts supplied:
-
Loosely fit left and right panels to left and right frame of bench.
-
Loosely fit rear panel with assistance if required.
-
Lay top panel (if supplied) on top of enclosure and bolt into position.
-
Tighten all bolts.