SECTION 2 – PERFORMANCE SPECIFICATIONS
2 – PERFORMANCE SPECIFICATIONS
2.1 – TRANSMITTER
Accuracy
. 0.25% of Natural S
pa
n, including hysteresis,
deadband, non-linearity, and non-repeat
a
bility.
Type
.
Differential pressure, flow, and mass flow.
Ranges
.
Natural Spans
Bi-Polar Natural Spans
0 to 25.00 IN w.c.
0 to 10.00 IN w.c.
–10.00 to 10.00 IN w.c.
0 to 5.00 IN w.c.
– 5.00 to 5.00 IN w.c.
0 to 2.00 IN w.c.
– 2.00 to 2.00 IN w.c.
0 to 1.00 IN w.c.
– 1.00 to 3.00 IN w.c.
0 to 0.50 IN w.c.
– 0.50 to 0.50 IN w.c.
0 to 0.25 IN w.c.
– 0.25 to 0.25 IN w.c.
0 to 0.10 IN w.c.
– 0.10 to 0.10 IN w.c.
0 to 0.05 IN w.c.
– 0.05 to 0.05 IN w.c.
Span Rangeability
. The calibrated s
pa
n can be down
ranged to 40% of the Natural S
p
an.
Stability
. ±0.5% of Natural S
p
an for six months.
Temperature Effect
.
Zero. None; corrected by
A
UTO-zero.
S
p
an. 0.015% of Natural S
p
an/ºF.
Mounting Position Effect
. None; corrected through
transmitter automatic zeroing.
Span and Zero Adjustment
. Digital, via internally
located pushbuttons.
Low Pass Filtration
. Response time to reach 98% of
a step change is adjustable from 0.5 to 256.0
seconds.
Overpressure and Static Pressure Limit
. 25 psig.
Automatic Zeroing
.
Accuracy. Within 0.1% of calibrated s
pa
n.
Frequency. Every 1 to 24 hours on 1 hour intervals.
Temperature Limits
. –20 to 180ºF
St
orage; +40 to
140ºF Operating.
Humidity Limits
. 0-95% RH, non-condensing.
2.2 – INDICATION
Display
. A backlit, graphical LCD providing single line of
data display. Also used for programming.
2.3 – OUTPUTS
Analog Output
. Single output linear to pressure, flow,
or massflow configurable via jumper to 0-5V , 0-10V, or
4-20mA.
2.4 – POWER
Power Supply
. S
t
andard 24VAC (16-30VAC) or 24VDC
(16-40VDC).
Power Consumption
. S
t
andard: 8VA at 24VAC; 6VA
at 24VDC.
Circuit Protection
. Power input is isolated, fused, and
reverse polarity protected.