SECTION 5 – OPERATION
5.7 – TRANSMITTER SCALING & CONFIGURATION
This Main Menu selection is where all application specific dat
a
is entered to configure the VE
LT
RON DPT 2500-
plus
for a unique application. Typical data includes: Process
T
ype, Process Units, Process Minimum/Maximum, and
Output Lockdown.
Note: Factory has entered data in this section based on customer supplied information. Dat
a c
an be reviewed and
verified by scrolling through the individual menu items or reviewing the Factory Set-Up Information sheet
provided with the unit. Review this information
BEFORE
making any changes, as they can have a significant
affect on the operation of the VELTRON DPT 2500-
plus
.
13
- EXIT User Setup
Trans. Scaling & Config.
- Low Pass Filter Selection
User Setup Main Menu
-
Square Root Off/On Selection
-
Process Type Selection
1
-
Process Units Selection
-
Process Format Selection
-
Process Minimum Selection
-
Process Maximum Selection
-
Output Lockdown Selection
1
-
Return to Main Menu
ON or OFF
Square Root Off/On
ON
Transmitter Flow
or
Transmitter Velocity
Process Type
TRANSMITTER FLOW
See UNITS list for
available selections
Process Units
F
LOW
CFM
See FORMAT list for
available selections
Process Format
FLOW XX,XXX CFM
-25000 to 25000
depends on process
Type and Format
Process Minimum
F
LOW
0 CFM
-25000 to 25000
depends on process
Type and Format
Process Maximum
F
LOW
10,000 CFM
0% to 100.00%
in 0.01 increments
Output Lockdown
10.00% FS Output
1 Available only if Square Root is ON.
If Square Root is OFF, Process Type is
Differential Pressure (D.P.).
Trans. Scaling & Configuration
Default selection shown.
Available selections:
Return to
MAIN MENU
Summary of Contents for VELTRON DPT 2500-plus