background image

page 4 of 16

GRAVITY DAMPER INFORMATION

ELECTRICAL REQUIREMENTS

The Cascade Series Whole-House Fan Systems require a 115 volt electrical power supply of minimum 15A am-
pacity and maximum 15 Amp circuit overcurrent protection. We strongly recommend providing a dedicated 
circuit for this fan system.

All electrical components, whether included with the Cascade system or supplied by others, must be rated 
for the fan system’s electrical load requirements; please refer to the Cascade Series specifi cations table for the 
electrical load requirements of the specifi c model to be installed.

All wiring and connections must be made according to this manual and all applicable electrical 
wiring codes and standards. All applicable electrical codes must be followed to the satisfaction of the local 
authority having jurisdiction.

Cascade Series Whole-House Fan Systems are shipped with a pre-wired 20 foot 115V power cord that may be 
used to operate the fan by means of a switched or remote-controlled 115V grounded outlet mounted in the 
attic. A wall switch rate for the fan system’s electrical load requirements may be mounted in the living space 
and used for simple single-speed control of the fan. The power cord is pre-wired to operate the fan on high 
speed only but may be re-wired for low speed operation if desired; please refer to the appropriate wiring dia-
grams for further information. If a remote-controlled outlet is used for fan control, the remote outlet must be 
rated for the electrical load requirements of the specifi c model to be installed. 

Cascade Series Whole-House Fan Systems include wall mount electrical control components including 2 multi-
speed switches, a white Decora duplex wall plate, and a plastic double gang wall box. These controls may be 
installed to provide multi-speed control of the fan from within the living space. Please refer to the appropriate 
wiring diagrams for further information on the proper wiring confi guration.

The 

The  Cascade

Cascade  Series  Whole  House  Fan  Systems    have  diff erent  gravity  damper  sizes,  depending  on  the

 Series Whole House Fan Systems  have diff erent gravity damper sizes, depending on the

specifi c  model  to  be  installed.    Verify  which  gravity  damper  size  is  provided  with  your  system  prior  to

specifi c model to be installed.  Verify which gravity damper size is provided with your system prior to
beginning installation of the product.

beginning installation of the product.

The Cascade Series fan systems include gravity-closed gravity damper doors that are opened by air
pressure created by fan operation. The dampers serve to block entry of air from the attic into the living space, and 
are provided with foam sealing and insulating material in the doors to reduce heat transfer from the attic space.

P/N 780105002  01/21  Rev A

Summary of Contents for CA6.5

Page 1: ...rk familiar with all the precautions required and has complied with all the requirements of the authority having jurisdiction Installation Date Installed By Phone P N 780105002 01 21 Rev A Cascade Series WHOLE HOUSE FAN SYSTEMS CA6 5 MODEL INSTALLATION MANUAL ITEMS INCLUDED 2 Fan Assembly with steel support straps hardware and 20 foot power cord 2 Duct Support Straps hardware 2 Acoustic Flex Duct ...

Page 2: ...page 2 of 16 P N 780105002 01 21 Rev A THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 3: ...y cated to maximize its effectiveness and efficiency The VENTILATION REQUIREMENTS section is also particularly important as it describes the minimum attic The VENTILATION REQUIREMENTS section is also particularly important as it describes the minimum attic ventilation neccessary to operate the fan ventilation neccessary to operate the fan The INSTALLATION GRAVITY DAMPER section contains important ...

Page 4: ...peed operation if desired please refer to the appropriate wiring dia grams for further information If a remote controlled outlet is used for fan control the remote outlet must be rated for the electrical load requirements of the specific model to be installed Cascade Series Whole House Fan Systems include wall mount electrical control components including 2 multi speed switches a white Decora dupl...

Page 5: ...ing ventilation be verified before it is installed Manufacturers typically publish their vents net free ventilation areas and or ratios in their products specification documents If this information is unavailable a ratio of 50 net free area to total area is usually a good rule of thumb A notable exception to this rule of thumb are ridge vents The industry standard net free ventilation area for rid...

Page 6: ...m their home s structure and contents This essentially pre cools the home ahead of the rise in temperature the next day which can reduce or even eliminate the need for air conditioning This CascadeWhole House Fan has been designed specifically for quiet and efficient operation As such we strongly recommend homeowners run this fan through the night to reduce their energy expense With these principl...

Page 7: ...nd engaging with the opening of the damper assembly 2 Using the cardboard from the fan system s packaging or other suitable material make a rectangular tem plate for the rough opening of the damper assembly to these dimensions making sure all sides are at right angles to each other a Cascade CA 6 5 model 14 1 4 wide 36 1 4 long FIGURE 1 TEMPLATE 3 Take the template into the attic above the general...

Page 8: ... other building elements of concern into hidden wiring plumbing or other building elements of concern 11 From below install drywall screws through the ceiling and through the flanges of the damper assembly and into any addition framing positioned above the flanges Use care to avoid installing screws outside of the area that will be covered by the eggcrate inlet grille 12 Hold the eggcrate grille i...

Page 9: ...upstream end of the duct to be as loose as possible Squeeze and position the flexible acoustic duct collar over the oval shaped collar on the damper box and attach using 3 of the screws provided or other suitable screws Note that twisting the duct will cause the fan to try to roll out of position Seal the joint with approved duct tape mastic or other approved means 4 Lift and support the fan assem...

Page 10: ...ic outlet box provided in the desired location 2 Run a 15 amp 115 VAC power circuit to the plastic outlet box installed in the living space using romex 14 2 with ground wire minimum Refer to minimum ampacity and maximum overload protection requirements listed for this power run Note a dedicated circuit is recommended Note Romex wire is defined as wire Gauge of conductors ie 14 2 14 3 Always use Ro...

Page 11: ...page 11 of 16 DIAGRAM 1 For CA6 5 Models Hardwired to Fan Assembly DIAGRAM 2 For CA6 5 Models with Dual 2 Speed Wall Controls P N 780202604 RevA P N 780202603 RevA P N 780105002 01 21 Rev A ...

Page 12: ...one of the 2 fan assemblies Switch the fan speed switches to the desired fan speed Each switch controls one of the 2 fan assemblies use them in conjunction to reach the desired speed setting use them in conjunction to reach the desired speed setting The fan will turn off if both speed switches are switched to off The fan will turn off if both speed switches are switched to off P N 780105002 01 21 ...

Page 13: ...ep the area in front of the fan as unobstructed as possible no object should be closer than 24 to the face of the fan This fan has been factory tested If problems are encountered please take a few moments to run through the following troubleshooting procedures before calling for assistance If the fan does not turn on check power to the unit and the wiring at both ends of the switch and the fan mou...

Page 14: ...52 SPECIFICATIONS Due to our continual product improvement efforts performance ratings and specifications are subject to change without notice Attic Net Free Ventilation and Open Window Ventilation Areas are listed as minimum requirements Actual lower ventilation areas may reduce fans overall performance at high speeds PART MODEL DESCRIPTION 602604201 AH WTT Digital Wall Timer Temp Ctl w RJ12 Cabl...

Page 15: ...page 15 of 16 P N 780105002 01 21 Rev A FIGURE 6 CASCADE CA6 5 REPLACEMENT PARTS P N 780800600 RevA ...

Page 16: ...S RESULTING FROM THE USE OF PRODUCT Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you b THIS WARRANTY AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES REMEDIES AND CONDITIONS WHETHER ORAL WRITTEN EXPRESS STATUTORY OR IMPLIED TO THE EXTENT PERMITTED BY LAW COMPANY DISCLAIMS ALL IMPLIED ...

Reviews: