51
0
Normal
1 x
o
x
x
The failure for
temperature
sensor of
outdoor coil
a.
The outdoor temperature
sensor loose;
b.
the outdoor temperature
sensor is failure;
c.
The indoor control board is
failure
2
★
Compressor
exhaust
temperature
sensor in
trouble
a.
the compressor exhaust
temperature sensor connect
loose;
b.
the compressor exhaust
temperature sensor is failure;
c.
the outdoor control board is
failure
5
★
IPM module
protection
a.
The IPM board is failure;
b.
The outdoor fan is broken;
c.
The outdoor fan motor is
failure;
d.
The outdoor fan has been
blocked ;
e.
The condenser is dirty;
f.
The outdoor unit has been
installed without standard.
6
★
★
AC voltage
higher or lower
protection
a.
the supply voltage is higher
or lower than normal;
b.
the inner supply voltage of
the unit is higher or lower than
normal
7
★
★
Communication
failure between
the indoor unit
and outdoor
unit
a.
the communication cable
connect loose;
b.
the communication cable is
failure;
c.
the connection between the
filter board and the outdoor
control board is incorrect or
loose;
d.
the connection between the
filter board and the terminal is
incorrect or loose;
e.
the indoor control board is
failure;
f.
the PFC board is failure;
g.
the power board is failure;
h.
the outdoor control board is
failure.
Summary of Contents for ABXCI4H4S0
Page 15: ...15 Outdoor 1854707...
Page 20: ...20 L1 04...
Page 21: ...21 Function Instruction 1 Major general technical parameters...
Page 63: ...63 3 4...
Page 64: ...64 5...
Page 65: ...65...
Page 66: ...66 DC fan motor test point...
Page 68: ...68 6 test point Check the screw of IPM fastening...
Page 70: ...70 test point The resistance of the compressor U W V W 7 SI and N test point...