48
Outdoor
EEPROM in
trouble
★
★
★
a.
he EEPROM chip is loose;
b.
the EEPROM chip inserted with opposite
direction;
c.
the EEPROM chip is failure
Compressor
exhaust
temperature too
high protection
O
★
a.
the compressor exhaust temperature sensor is
failure;
b.
the refrigerant of the unit is not enough
Outdoor ambient
temperature
sensor in trouble
★
★
a.
the outdoor ambient temperature sensor
connect loose;
b.
the outdoor ambient temperature sensor is
failure;
c.
the outdoor control board is failure
Compressor shell
temperature too
high protection
★
O
a.
the compressor exhaust temperature sensor
connect loose
b.
the refrigerant of the unit is not enough
Anti-freeze
protection with
cooling or
overload
protection with
heating in indoor
unit
O
O
a.
the indoor coil temperature sensor connect
loose;
b.
the indoor coil temperature sensor is failure;
c.
the indoor control board is failure
d.
the refrigerant system is abnormal.
Compressor drive
in trouble
O
O
a.
the outdoor drive board is failure;
b.
the compressor is failure
c.
the outdoor control board is failure
Outdoor fan motor
locked rotor
protection
O
O
★
a.
the connection of the outdoor fan motor is loose;
b.
there are something block the outdoor fan;
c.
the fan motor is failure;
d.
the outdoor control board is failure
Outdoor coil
anti-overload
protection with
cooling
★
a.
the refrigerant is too much;
b.
the outdoor fan motor is failure;
c.
the outdoor fan is broken;
d.
the condenser is dirty;
e.
the air inlet and air outlet of the indoor unit and
the outdoor unit is not normally
Summary of Contents for ABXCI4H4S0
Page 15: ...15 Outdoor 1854707...
Page 20: ...20 L1 04...
Page 21: ...21 Function Instruction 1 Major general technical parameters...
Page 63: ...63 3 4...
Page 64: ...64 5...
Page 65: ...65...
Page 66: ...66 DC fan motor test point...
Page 68: ...68 6 test point Check the screw of IPM fastening...
Page 70: ...70 test point The resistance of the compressor U W V W 7 SI and N test point...