17
Condition
Enter Condition
Leave condition
Speed
HEAT SINK
T ≤ 140℉
T > 149℉
OFF
TEMPERATURE
149℉≤ T < 185℉
T ≤ 140℉ or T ≥ 185℉
50%
T > 185℉
T ≤ 176℉
100%
CHARGER
CURRENT
I ≤ 15%
I ≥ 20%
OFF
20%< I ≤ 50%Max
I≤ 15% or I > 50%Max
50%
I > 50%Max
I ≤ 40%Max
100%
LOAD Percentage
(INV MODE)
Load < 30%
Load ≥ 30%
OFF
30% ≤ Load < 50%
Load ≤ 20% or Load ≥ 50%
50%
Load ≥ 50%
Load ≤ 40%
100%
Allow at least 12 inches of clearance around the inverter for air flow. Make sure that the air can circulate
freely around the unit.
Fan noise level <60db at a distance of 3 feet
2.5.11 DIP Switches
On the DC end of inverter, there are 5 DIP switches that enable users to customize some of the inverter
charger's functions.
Switch NO
Switch Function
Position: 0
Position: 1
SW1(Utility Priority)
Low Battery Trip Point
10.0VDC
10.5VDC
SW1(Battery Priority)
10.5VDC
11.5VDC
SW2(230V)
AC Input Range
184-253VAC
154-264VAC(40-70Hz)
SW2(120V)
AC Input Range
100-135VAC
90-135VAC(40-70Hz)
SW3
Power Save Override
Inverter Off
Saver On 3 sec
SW4
Frequency Switch
50Hz
60Hz
SW5
Battery/AC Priority
AC Priority
Battery Priority
Low Battery Trip Volt (SW1)
Deep discharge of the lead acid battery will cause losses in capacity and early aging. In some applications a
different low voltage disconnection level may be preferred. For example, in solar applications, users may
intend to have less DOD to prolong the battery life cycle. While for mobile applications, users may intend to
have more DOD to fully use the battery capacity available, minimizing on- board weight.
For 12VDC models, the Low Battery Trip Volt is set at 10.0VDC by default. It can be customized to
10.5VDC using SW1. This is to prevent batteries from over-discharging while there is only a small load
applied on the inverter.
multiply*2 for 24VDC, multiply*4 for 48VDC
AC Input Range (SW2)
There are different acceptable AC input ranges for different kinds of loads.
For some relatively sensitive electronic devices, a narrow input range of 184-253VAC (100-135V for
120VAC model) is required to protect them.
While for some resistive loads that work in a wide voltage range, the input AC range can be customized to
154-264VAC (90-135V for 120VAC model). This helps to power loads with the most AC input power
without frequently switching to the battery bank.
Summary of Contents for Global LF Series
Page 2: ......
Page 17: ...15 2 5 8 LED Indicator Lights Status ...
Page 29: ...27 3 6 Install Flange 1000W 1500W Models 2000W 3000W Models 4000W 6000W Models ...
Page 30: ...28 DC Side View ...
Page 36: ...34 ...
Page 38: ...36 Appendix 2 Installation Diagram DC shunt is not required ...
Page 39: ......
Page 40: ...614 01206 09 ...