background image

6

Limitations of Smoke / Heat Alarms

Use the Smoke / Heat Alarm Test buttons “> <” to 
familiarise your family with the Alarm sound and to 
practice fire drills regularly with all family members. Draw 
up a floor plan that will show each member at least 2 
escape routes from each room in the house.

Children tend to hide when they don’t know what to do. 
Teach children how to escape, open windows, and use 
roll up fire ladders and stools without adult help. Make 
sure they know what to do if the alarm goes off.

1.

 Check room doors for heat 

or smoke.  Do not open a hot 
door. Use an alternate escape 
route. Close doors behind you 
as you leave.

2.

 If smoke is heavy, crawl out, 

staying close to floor. Take 
short breaths, if possible, 
through a wet cloth or hold 
your breath. More people die 
from smoke inhalation than 
from flames.

3.

 Get out as fast as you can. 

Do not stop for packing. Have 
a prearranged meeting place 
outside for all family members. 
Check everybody is there.

4.

 Call the Fire Brigade 

 

immediately on a mobile 
phone or from a neighbour’s 
house.  Make sure to call 
the Brigade for  all fires no 
matter how small - fires can 
suddenly spread. Also call the 
Brigade even if the alarm is 
automatically transmitted to a 
remote manned centre - the 
link may have failed.

5.

 

NEVER

 re-enter a burning house.

Smoke / Heat Alarms have significantly helped to reduce 
the number of fire fatalities in countries where they are 
widely installed.

However independent authorities have stated that they 
may be ineffective in some circumstances. There are a 
number of reasons for this: 

•   NOTE: Constant exposure to high or low temperatures 

or high humidity may reduce the life of the battery.

•  Smoke / Heat Alarms will not detect fire if sufficient 

smoke / heat does not reach the Alarm. Smoke / heat 
may be prevented from reaching the Alarm if the fire is 
too far away, for example, if the fire is on another floor, 
behind a closed door, in a chimney, in a wall cavity, 
or if the prevailing air draughts carry the smoke / heat 
away.  Installing Smoke / Heat Alarms on both sides 
of  closed doors and installing more than one Smoke 

Planning Your Escape Route

NEVER

Summary of Contents for Ei160e Series

Page 1: ...Rechargeable Battery Backup Ei Electronics 2018 P N B18148 Rev4 Aico Ltd Mile End Business Park Maesbury Rd Oswestry Shropshire SY10 8NN U K Tel 01691 664100 www aico co uk Ei Electronics Shannon Co...

Page 2: ...n decorating to prevent dust or other contamination damaging the unit Clean your Alarm regularly RF Interconnection The Ei160e series is supplied with an Easi Fit base that allows very quick and simpl...

Page 3: ...l the units should alarm within 10 seconds of the first horn sounding The red light on the first unit only will flash about once a second On releasing the button the local Alarm will stop sounding imm...

Page 4: ...returned to the manufacturer for repair or replacement see Service and Guarantee section Cleaning WARNING Electrical shock hazard Disconnect the AC mains at the fuse box or circuit breaker powering th...

Page 5: ...ilenced by disconnecting the mains power and removing the unit see ALARM REMOVAL section page 11 Installer If cleaning the Alarm does not correct the problem it can be returned to the manufacturer for...

Page 6: ...Call the Fire Brigade immediately on a mobile phone or from a neighbour s house Make sure to call the Brigade for all fires no matter how small fires can suddenly spread Also call the Brigade even if...

Page 7: ...e of purchase Ei Electronics guarantees this Alarm for five years from date of purchase against any defects that are due to faulty materials or workmanship This guarantee only applies to normal condit...

Page 8: ...d replace the unit 1 If the green mains light is on and recharging the Lithium cells or cleaning the unit has not stopped the beeps a fault may exist Disconnect the mains first and replace the unit se...

Page 9: ...local government office or the retailer where you purchased this product Ei Electronics Shannon Co Clare Ireland Nominal activation conditions sensitivity response delay response time and performance...

Page 10: ...10...

Page 11: ...GES SLIDE ON ALARM 3 LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW INSERT A FLAT BLADED SCREWDRIVER HORIZONTALLY APPROX 1cm INTO THE CENTRE OF THE REMOVA...

Page 12: ...false alarms are minimised to ensure the units are not disabled or ignored The BS standard gives guidance on how many Alarms to install what type of Alarm to use where to position Alarms The above po...

Page 13: ...ets or bathroom Minimum Protection LD3 Alarms in all hallways stairways and circulation areas that form part of the escape routes from the dwelling UK Requirements BS 5839 6 2013 Interconnect all Alar...

Page 14: ...and all high fire risk areas rooms e g kitchen living rooms garages and all bedrooms apart from toilets or bathroom Interconnect all Alarms Heat Alarms located in Heat Alarms must be within 5 3m of p...

Page 15: ...In enclosed kitchens with doors closed 5 Greatly depends on ventilation and distance from source of fumes Grade D System The mains powered Smoke and Heat Alarms with battery back up covered by these...

Page 16: ...tom of the detection element is above the level of any door openings Wall mounting should only be considered where close spaced beams or similar obstructions may preclude ceiling mounting It is consid...

Page 17: ...n built in terminal block to connect it to the mains The mounting plate can be screwed directly to the ceiling Alternatively it can be screwed to a standard junction box It requires a current of 40mA...

Page 18: ...s should be connected on a single final circuit unless the means of interconnection is by radio signals e g RadioLINK See BS 5839 6 2013 for further information Note The Ei100MRF RadioLINK Module can...

Page 19: ...are two other positions which are also suitable for the surface wiring to enter and exit the alarm one next to the removable section and another directly opposite 5 Carefully align the mounting plate...

Page 20: ...NG Do not connect these Alarms to any other model produced by another manufacturer Doing so may damage the Alarms and could result in a shock or fire hazard Wiring must be installed in compliance with...

Reviews: