background image

19

• check that the Interconnect wire is NOT connected to 

Live, Neutral or Earth. 

Do not use an Earth wire for 

the Interconnect line.

N.B. The Alarm does not need to be earthed. However the 
terminal marked        is provided for the convenience of the 
installer so that any copper Earth wire or cable coloured 
green & yellow, can be safely terminated.

To interconnect the Alarms connect all the IC terminals 
together as shown in 

Figure 6

.

4.

 If the mains wires are recessed, bring the wires 

through the rear hole in the mounting plate as shown 
in 

Figure 4

.

If the mains wires are being brought along the surface:

(a) position the mounting plate so the cable trunking is 
as shown in 

Figure 4

.

(b) the mounting plate has a removable section, take it out 
to interface directly with 25mm conduit as shown in 

Figure 

5

. If interfacing to 16mm conduit carefully cut around the 

marked section, leaving the top intact and replace the 
section. (If you are not using surface wiring, the removable 
section must be left in place for electrical safety reasons).

There are two other positions which are also suitable for 
the surface wiring to enter (and exit) the alarm, one next 
to the removable section and another directly opposite.

5.

 Carefully align the mounting plate and screw into 

place. Connect the wires to the terminal block. With 
recessed wiring, ensure the rear gasket seals around the 
edge of the hole in the ceiling or wall. This is to prevent 
air draughts affecting the smoke/heat entering the 
Alarm. If the hole is too large or the Alarm does not seal 
it, it should be sealed with silicone rubber or equivalent. 
Replace the wiring cover.

6.

 Carefully line up the unit on the base and slide on.

7.

 Press and hold the “> <” button for 10 seconds. The horn 

will sound. On release of the button the local alarm will stop 
sounding immediately and the interconnected Alarms will 
stop sounding a few seconds later.

8.

 Connect the mains power to the Alarm circuit. Check 

the green light is on. 

9.

 Attach the 

‘Smoke Alarm’

 identification label provided 

to the distribution board to identify the alarm circuit.

10.

 Attach the 

‘Mains Smoke / Heat Alarms’

 label 

provided on or near the distribution board and write in 
date installed and the number of Alarms on the circuit.

REMOVEABLE

TRUNKING DOOR FOR

Figure 4

Figure 5

Summary of Contents for Ei160e Series

Page 1: ...Rechargeable Battery Backup Ei Electronics 2018 P N B18148 Rev4 Aico Ltd Mile End Business Park Maesbury Rd Oswestry Shropshire SY10 8NN U K Tel 01691 664100 www aico co uk Ei Electronics Shannon Co...

Page 2: ...n decorating to prevent dust or other contamination damaging the unit Clean your Alarm regularly RF Interconnection The Ei160e series is supplied with an Easi Fit base that allows very quick and simpl...

Page 3: ...l the units should alarm within 10 seconds of the first horn sounding The red light on the first unit only will flash about once a second On releasing the button the local Alarm will stop sounding imm...

Page 4: ...returned to the manufacturer for repair or replacement see Service and Guarantee section Cleaning WARNING Electrical shock hazard Disconnect the AC mains at the fuse box or circuit breaker powering th...

Page 5: ...ilenced by disconnecting the mains power and removing the unit see ALARM REMOVAL section page 11 Installer If cleaning the Alarm does not correct the problem it can be returned to the manufacturer for...

Page 6: ...Call the Fire Brigade immediately on a mobile phone or from a neighbour s house Make sure to call the Brigade for all fires no matter how small fires can suddenly spread Also call the Brigade even if...

Page 7: ...e of purchase Ei Electronics guarantees this Alarm for five years from date of purchase against any defects that are due to faulty materials or workmanship This guarantee only applies to normal condit...

Page 8: ...d replace the unit 1 If the green mains light is on and recharging the Lithium cells or cleaning the unit has not stopped the beeps a fault may exist Disconnect the mains first and replace the unit se...

Page 9: ...local government office or the retailer where you purchased this product Ei Electronics Shannon Co Clare Ireland Nominal activation conditions sensitivity response delay response time and performance...

Page 10: ...10...

Page 11: ...GES SLIDE ON ALARM 3 LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW INSERT A FLAT BLADED SCREWDRIVER HORIZONTALLY APPROX 1cm INTO THE CENTRE OF THE REMOVA...

Page 12: ...false alarms are minimised to ensure the units are not disabled or ignored The BS standard gives guidance on how many Alarms to install what type of Alarm to use where to position Alarms The above po...

Page 13: ...ets or bathroom Minimum Protection LD3 Alarms in all hallways stairways and circulation areas that form part of the escape routes from the dwelling UK Requirements BS 5839 6 2013 Interconnect all Alar...

Page 14: ...and all high fire risk areas rooms e g kitchen living rooms garages and all bedrooms apart from toilets or bathroom Interconnect all Alarms Heat Alarms located in Heat Alarms must be within 5 3m of p...

Page 15: ...In enclosed kitchens with doors closed 5 Greatly depends on ventilation and distance from source of fumes Grade D System The mains powered Smoke and Heat Alarms with battery back up covered by these...

Page 16: ...tom of the detection element is above the level of any door openings Wall mounting should only be considered where close spaced beams or similar obstructions may preclude ceiling mounting It is consid...

Page 17: ...n built in terminal block to connect it to the mains The mounting plate can be screwed directly to the ceiling Alternatively it can be screwed to a standard junction box It requires a current of 40mA...

Page 18: ...s should be connected on a single final circuit unless the means of interconnection is by radio signals e g RadioLINK See BS 5839 6 2013 for further information Note The Ei100MRF RadioLINK Module can...

Page 19: ...are two other positions which are also suitable for the surface wiring to enter and exit the alarm one next to the removable section and another directly opposite 5 Carefully align the mounting plate...

Page 20: ...NG Do not connect these Alarms to any other model produced by another manufacturer Doing so may damage the Alarms and could result in a shock or fire hazard Wiring must be installed in compliance with...

Reviews: