Recommendations for the Quality of Water 

(Primary circuit)

To prevent the formation of scale and sludge in a 

closed heating circuit through the penetration of 

oxygen and carbonates, follow the recommenda-

tions below:

 

î

Before fi lling the system, clean it according to 

standard EN14336. Chemical cleaning agents 

can be used.

 

î

If the circuit is in bad condition, or the cleaning 

operation was not effi  cient, or there is a large 

volume of water in the system (e.g. cascade), 

it is recommended to separate the appliance 

from the heating circuit using a plate heat ex-

changer or an equivalent accessory. In that 

case, it is recommended to install a hydrocy-

clone or magnetic fi lter on the system side.

 

î

Limit the fi ll operations. To control the quantity 

of water added into the system, install a water 

meter on the fi lling line of the primary circuit. 

No more than 5% of the total content of the 

system is allowed annually.

 

î

Automatic  fi lling  systems  are  not  recom-

mended unless the fi ll frequency is checked 

and the levels of scale and corrosion inhibitor 

are maintained at an appropriate level.

 

î

If the system needs to be refi lled frequently, 

check for leaks in the primary circuit.

 

î

Inhibitors may be used according to stand-

ard EN 14868.

 

î

An air separator (on the appliance supply 

circuit) combined with a dirt separator (up-

stream of the appliance) must be installed 

according to the manufacturer’s instructions.

 

î

Additives can be used to keep the oxygen in 

solution in the water.

 

î

Use the additives in accordance with the in-

structions of the manufacturer of the water 

treatment product.

Water Hardness

 

î

If the hardness of the fi ll water is higher than 

20° fH (11,2° dH), soften it. At commission-

ing, the water should be soft.

 

î

Check regularly the water hardness and en-

ter the values in the maintenance log sheet 

(provided at the end of the manual).

Water Parameters

 

î

In addition to the oxygen and the water hard-

ness, other parameters of the water must be 

checked. Treat the water if the measured val-

ues are outside the range of the table below.

 

î

AIC recommends to have the DHW circuit 

operating at more than 60°C to prevent the 

development of bacteria in the DHW circuit.

Water Parameters

Range

Acidity

8.2 < pH < 9.0

Conductivity

< 400 μS/cm (at 25°C)

Chlorides

< 125 mg/l

Iron

< 0,5 mg/l

Copper

< 0,1 mg/l

Water hardness

°fH

°dH

mmolCa(HCO3)2 / l

Very soft

0 - 7

0 - 3.9

0 - 0.7

Soft

7  - 15

3.9 - 8.4

0.7 - 1.5

Fairly hard

15 - 25

8.4 - 14

1.5 - 2.5

Hard

25 - 42

14 - 23.5

2.5 - 4.2

Very hard

> 42

> 23.5

> 4.2

Summary of Contents for SILOX S

Page 1: ...h e a t i n g s y s t e m s EN installation and maintenance manual FOR THE INSTALLER AND THE USER 90 130 190 260 400 600 1000 L DOMESTIC HOT WATER STAINLESS STEEL TANKS I10_092 01 SILOX S SILOX S...

Page 2: ...operation of the appliance and the hydraulic system as well as the safety devices that are provided Any instruction regarding periodic checks to be performed and possible anomaly to be reported All t...

Page 3: ...ts 11 Recommendations for the Quality of Water Primary circuit 12 Hydraulic Connections 13 Commissioning 14 Filling the Tank 14 Starting Up 14 Maintenance 15 Safety Instructions and Recommendations 15...

Page 4: ...r injuries or death Indicates an important instruction which if not followed could re sult in a hazardous situation that could cause damage to equip ment and or injuries Indicates an essential instruc...

Page 5: ...or written consent of the manufacturer If components need to be replaced only genuine factory parts or compo nents approved by the manufacturer must be used When working on the appliance and the syste...

Page 6: ...and hole 2 Thermal insulation 3 Drywell for temperature sensor 4 DHW inner storage tank in stainless steel 5 Steel primary outer tank 6 Primary connection return 7 Base cover 8 Inspection hole 9 Dip t...

Page 7: ...170 182 182 182 192 336 D 575 980 777 1027 1512 1493 1926 Connections in SX90S SX130S SX190S SX260S SX400S SX600S SX1000S Cold water inlet M G 3 4 G 3 4 G 3 4 G 3 4 G 1 G 1 G 11 4 DHW outlet M G 3 4 G...

Page 8: ...pty weight Kg 35 51 64 78 106 151 239 Standing heat loss W 45 50 58 63 99 103 113 Energy efficiency class B B B B C C C Hydraulic Performance SX90S SX130S SX190S SX260S SX400S SX600S SX1000S Peak Flow...

Page 9: ...and temperatures of the primary circuit for DHW production from 10 C to 45 C Performance and pressure losses 86 Pressure losses between input and output connections of the primary circuit for differen...

Page 10: ...the electrical circuit isolate the electri cal supply of the appliance through the external power cutting device fuse circuit breaker etc All connections must be carried out in accordance with curren...

Page 11: ...appli ance power and the system size and the increase in temperature and pressure Using antifreeze in the primary circuit will reduce the heating performance The higher the concentration of antifreeze...

Page 12: ...eds to be refilled frequently check for leaks in the primary circuit Inhibitors may be used according to stand ard EN 14868 An air separator on the appliance supply circuit combined with a dirt separa...

Page 13: ...f tap DHW Outlet Isolating valve Cold water inlet Thermostatic mixing valve Pressure reducing valve Motorised spring return valve or manual valve From distribution network Make sure that your hydrauli...

Page 14: ...d 1 5 bar Follow on Task s Check that there are no leaks Start the boiler as required Refer to the Start up procedure opposite Always fill and pressurise the inner tank DHW before filling the outer pr...

Page 15: ...ne factory parts or parts approved by the manu facturer Replace any gaskets or seals present on the removed components before reinstallation unless otherwise speci ed in the procedures Operate manuall...

Page 16: ...is sound Gradually introduce the descaling agent until the correct amount is added for the volume of water Run the pump and monitor the pH value the pro cess is complete when the pH stabilises at less...

Page 17: ...an be extremely hot Use extreme care when draining a hot appliance Draining procedure Always drain depressurize the outer tank before draining the inner tank to prevent any deformation of the inner ta...

Page 18: ...refer to the heat generator manual The isolating valves of the primary circuit are closed 2 Open the isolating valves to allow prima ry water to fill the outer tank Make sure that the DHW in ner tank...

Page 19: ...uct Fiche AIC SILOX S Referring to Commission Delegated Regulation No 812 2013 Model Energy efficiency class Standing loss Volume SX90S B 45 W 80 l SX130S B 50 W 122 l SX190S B 58 W 187 l SX260S B 63...

Page 20: ...AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands www myaic eu...

Reviews: