Chapter 3 Sub-System configuration Setup
J2024-01 User's Manual
38
3.4.10 How to power off/on all disk drives manually
The "RQST ON" for Power Supply is defined in the bit5, byte3 of the "Power
Supply control element" in the SES-3 specification. Clear the bit to power
off all disk drives. Set the bit to power on all disk drives. Please install the
software package "sg3_utils" on your host computer, and have a SAS HBA
and a cable to connect your host with the expander. We use Linux for
example.
(A) Show the device for AIC Expander Controller (canister)
$ sg_map -i
/dev/sg2 AIC 12G 2U24SAS3swap 0c01
(B) Power off all disk drives
$ sg_ses --descriptor=DiskPowerSupply --clear=3:5:1 /dev/sg2
(C) Power on all disk drives
$ sg_ses --descriptor=DiskPowerSupply --set=3:5:1 /dev/sg2
Summary of Contents for J2024-01
Page 1: ...D N MAN 00304 C P N H882JKC000 00010 J2024 01 SAS SATA JBOD SERIES User s Manual...
Page 11: ...5 J2024 01 User s Manual Chapter 1 Product Introduction Rear Panel...
Page 39: ...J2024 01 User s Manual 33 Chapter 3 Sub System configuration Setup...
Page 40: ...Chapter 3 Sub System configuration Setup J2024 01 User s Manual 34...
Page 41: ...J2024 01 User s Manual 35 Chapter 3 Sub System configuration Setup...
Page 42: ...Chapter 3 Sub System configuration Setup J2024 01 User s Manual 36...
Page 43: ...J2024 01 User s Manual 37 Chapter 3 Sub System configuration Setup...
Page 45: ...J2024 01 User s Manual 39 Chapter 3 Sub System configuration Setup...
Page 46: ...Chapter 3 Sub System configuration Setup J2024 01 User s Manual 40...
Page 47: ...J2024 01 User s Manual 41 Chapter 3 Sub System configuration Setup...
Page 90: ...Chapter 4 BMC Configuration and Setting J2024 01 User s Manual 84...