37
RC SERIES INSTALLATION MANUAL
LonWorks Name
SNVT Type
SNVT Index
SCPT Reference
SCPT Index
UCPT Index
Occupied Cooling Setpoint Input (Read/Write)
Standby Cooling Setpoint Input (Read/Write)
Unoccupied Cooling Setpoint Input (Read/Write)
Occupied Heating Setpoint Input (Read/Write)
Standby Heating Setpoint Input (Read/Write)
Unoccupied Heating Setpoint Input (Read/Write)
nciMinClgSetpt
SNVT_temp_p
105
4
Minimum Cooling Setpoint Input (Read/Write)
nciMaxHtgSetpt
SNVT_temp_p
105
3
Maximum Heating Setpoint Input (Read/Write)
nvoSpaceTemp
SNVT_temp_p
105
Space or Zone Temperature Value (Read Only)
nvoDischAirTemp
SNVT_temp_p
105
Discharge Air Temp
Field Supplied Only
(Read Only)
nvoEffClgSetpt
SNVT_temp_p
105
Effective Cooling Setpoint Value (Read Only)
nviSpaceTemp
SNVT_temp_p
105
Space or Zone Temperature Value Override(Write)
nvoEffHtgSetpt
SNVT_temp_p
105
Effective Heating Setpoint Value (Read Only)
nciAux5LevP
SNVT_lev_percent
81
Dehumidification Setpoint (Read/Write)
nciAux1Temp
SNVT_temp_p
105
147
Heating Freeze Protection Temperature Setpoint Value (Read/Write)
nciAux2Temp
SNVT_temp_p
105
148
Heating Freeze Protection Temperature Setpoint Value (Read/Write)
1st Stage Compressor Heating Output (Read Only)
1st Stage Compressor Cooling Output (Read Only)
Fan Output (Read Only)
Unit Mode of Operation (Read Only)
Unit Alarm mode (Read Only)
nciPropBand
SNVT_temp_diff_p
147
177
Heating/Cooling Prop Band Input (Read/Write)
nciRemoteSetptMin
SNVT_temp_diff_p
147
98
Warm/Cool Adjust Span (Read/Write)
nciRemoteSetptMax
SNVT_temp_diff_p
147
97
Warm/Cool Adjust Offset Value (Read/Write)
nciTempOffset
SNVT_temp_diff_p
147
11
Space or Zone Temperature Sensor Calibration Input (Read/Write)
nviSetpoint
SNVT_temp_p
105
General Setpoint Input (Read/Write)
nvoHtgFrzPro1Tmp
SNVT_temp_p
105
Heating Freeze Sensing Temperature Value (Read Only)
nvoHtgFrzSetpt
SNVT_temp_p
105
Heating Freeze Sensing Temperature Setpoint Value (Read Only)
nvoAlarms
SNVT_lev_cont
21
Alarms Enumerated [0=no alarms, 1=condensate alarm, 2=Compressor Hi Discharge
Pressure alarm, 3=Compressor low Suction Pressure alarm, 4=Freeze sensing
alarm, 8=Faulty Freeze Sensor alarm,
9=Loss of Charge]
(Read Only)
nvoPWMOut
SNVT_volt
44
ECM PWM Control signal value (Read Only)
nvoECMOvrd
SNVT_volt
44
ECM PWM Control signal Override (Read/Write)
nvoHumidity
SNVT_volt
44
Space Humidity value (Read Only)
nviAO2
SNVT_lev_percent
81
Spare PWM Output AO2 Command (Write)
nvoAO2
SNVT_lev_percent
81
Spare PWM Output AO2 Value (Read Only)
nciBypassTime
SNVT_time_min
123
SCPTbypassTime
34
Temporary Occupancy Time Period Input (Read/Write)
nvoEffectOccup
SNVT_occupancy
109
Effective Occupancy State (Read Only)
nviOccManCmd
SNVT_occupancy
109
Occupancy Override Command Input (Read/Write)
nviEmergOverride
SNVT_hvac_emerg
103
Emergency Override Input (Read/Write)
nvoFanStatus
SNVT_lev_disc
22
Fan Output Status (Read Only)
nvoAccStatus
SNVT_lev_disc
22
Accessory 2 Output Status (Read Only)
nvoLP_WVStatus
SNVT_lev_disc
22
Accessory 1 Output Status (Read Only)
nvoAlarmStatus
SNVT_lev_disc
22
Alarm Output Status (Read Only)
nviAlarmReset
SNVT_lev_disc
22
Alarm Reset Input (Read/Write)
nviFanSpeedCmd.StateSNVT_switch
95
Network equivelant of a thermostatic 'G' call. (Write)
nviComprEnable.State SNVT_switch
95
Network equivelant of a thermostatic 'Y1' call. (Write)
nviComprEnable.State SNVT_switch
95
Network equivelant of a thermostatic 'Y2' call. (Write)
nvoRV1Status
SNVT_lev_disc
22
Reversing Valve Output Status (Read Only)
nviOccSchedule
SNVT_tod_event
128
Occupancy Supervisory Scheduler Command Input (Read/Write)
nvoCompFanProv
SNVT_lev_disc
22
Compressor/Fan Proving Switch Status (Read Only)
nvoDirtyFilter
SNVT_lev_disc
22
Dirty Filter Switch Status (Read Only)
nvoComp2Status
SNVT_lev_disc
22
Compressor Hi Capacity Command Status (Read Only)
nviBO5
SNVT_lev_disc
22
Command for output BO5 used for Emg Heat-Interlocked with Fan DP9Read/Write)
nviBO9
SNVT_lev_disc
22
Command for output BO9(Read/Write)
nvoBO5
SNVT_lev_disc
22
Value output for BO5 used for Emg Heat (Read Only)
nvoBO9
SNVT_lev_disc
22
Value output for BO9 (Read Only)
nviDehumEna.State
SNVT_lev_disc
22
Dehumidification command-like a Humidistat (Read/Write)
Point Description
60
LonWorks
SCPTsetPnts
nciSetpoints
SNVT_temp_setpt
106
nvoUnitStatus
SNVT_hvac_type
112
LonWorks
Controls - FX10 cont.