10
At least 1 1/4 inch (31.8mm) clear
Select the installation location that provides easy access to the indoor unit.
1. Make sure the location can support at least four times the weight of the unit.
2. Secure the outdoor unit on the selected base location with expansion screws.
3. The outdoor unit should be installed at least 1 1/4 inch above the ground or base in order
to install a drain pipe and connector (shown below).
1. The outdoor unit(s) should be located where condensate poses no hazard or safety risk.
Each unit is supplied with a drain pipe connector.
2. Before installing the drain pipe fitting, appropriately plug all other base pan holes not
used.
3. Install the drain pipe fitting into the appropriate hole located at the base of the unit and
then connect the drain pipe to it.
Condensate Management of the Outdoor Unit
Foot holes
Foot holes
Installation
4. Place the outdoor unit on the support base.
5. Secure the foot holes of the outdoor unit with bolts (shown below).