![background image](http://html1.mh-extra.com/html/ahri/4mxa2024a10nua/4mxa2024a10nua_installer-manual_2870542009.webp)
9
A
B
C
D
E
G
4TXD2060A10NUA
42-3/4
(1085)
16-7/8
(427)
53-3/4
(1365)
24-1/2
(620)
15-1/2
(395)
14-1/2
(370)
Dimensions
Model
Unit: inch(mm)
4TXD2060A10NUA
Installation
>
12(305)
>
20(508)
>
79(2000)
>
12 (305)
>
12(305)
>
20(508)
>
79(2000)
Unit: inch (mm)
WARNING
1.
Install the unit on a level surface or on supports that are level.
2.
If the location is subject to strong winds, the additional force must be accounted for and the
unit must be fixed securely to the base. Refer to local codes for additional requirements.
When the outdoor unit is surrounded by walls or other obstructions, the installation space
of the unit should be no less than the clearances indicated below. For efficient operation,
leave three of four directions of peripheral constructions open when possible.
Unit Installation
NOTICE
The outdoor unit does not have a TXV (thermal expansion valve), please make sure there is a
throttling valve (which throttles the unit when it operates in cooling mode and opens fully when it
operates in heating mode) in the indoor unit (air handler or A coil).
Outdoor Unit Installation