Service
Check and Maintenance
Maintenance is more economic than repairs. It helps in identifying malfunctions in time, ensures
continuous operation and longer service life of the device. Maintain and check the following assemblies
and components repeatedly, at the latest after every 12 months as described.
After 4500 operating hours the cooler automatically signals a service reminder. This is a
maximum value. We recommend a service after 3000 operating hours or 12 months,
whichever comes first. After 9000 operating hours a service alarm is activated (see chapter
“Temperature Monitoring and Error Diagnosis / Operation Status Indicators”).
Depending on operating conditions and operating hours the tubes of the condensate pumps
will show different degrees of wear. We recommend replacement of the pump hoses after
every 3 months as a precautionary measure.
Depending on the sample gas quality the filter (option) will show different degrees of
contamination. We recommend replacement of the filter cartridge every 3 months as a
precautionary measure.
Only qualified personnel should perform troubleshooting, maintenance or repair operations.
Make sure that maintenance personnel have read and understand the safety and operation
instructions in this manual.
Before attempting any maintenance operation on the cooler, shut it completely down (notice
chapter „Decommissioning“) and wait at least 10 minutes.
DANGER! Supply voltage!
Prior to performing any maintenance or service, be sure that no
part of the machine is powered.
DANGER! Condensate may be toxic or corrosive!
Please wear sufficient protective clothing
(for example safety gloves, face mask, safety goggles etc.).
CAUTION! Follow system and process-specific safety measures!
System and process-
specific safety measures must be followed before performing maintenance.
CAUTION! Toxic and explosive gases!
Corresponding guidelines must be adhered to while
operating with toxic and explosive gases.
WARNING! Open housing!
Never operate equipment with panels removed.