background image

Mini Merlin Installation, Operation & Maintenance                                                                                                                              

 

Rev: 03 05-22 

9  

Wiring 

 Pilot Water Heater & Boiler Limit Breaker 

 

The device can be used to directly shut the pilot of a water heater in an alarm or power failure state using a product 
from Field Controls. The BMS terminals may also be used to connect to a home alarm system. 

 

 

Wiring 

 Remote Shut Off 

 

Your mini-merlin can be integrated with remote devices with an open /close circuit via 
the Remote Shut-Off volt free switch terminal.  
 
This terminal has a factory fitted link installed. This terminal is normally closed and will 
alarm when energised open - isolating the gas supply.  

 
 
 
 

 

 
 

 
When using this input, only the mains utility output shall de-energize. If you are using the CO or NG relay to shut down 

a boilers external limit circuit, you will need to wire the input in series with the relay output. 

 

Auto Reset & Buzzer Switches 

 

 

ON 

OFF 

A

u

to

 

R

es

et

 

In the event of a power loss 

 the mini-merlin will restart 

automatically when power is restored.  

In the event of a power loss 

 the mini-merlin will need to 

be reset manually when power is restored. 

This is the factory default condition. 

B

u

zz

er

 

The buzzer will sound every 15 seconds during pre-alarm 

and continuously at alarm level. 

This is the factory default condition. 

The buzzer will not sound at any gas level. 

 

 

 

 

Summary of Contents for Mini Merlin LPGCO v2 TX

Page 1: ...O v2 TX Dual Gas Detector Installation Operation Maintenance Manual Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this...

Page 2: ...uits 8 Wiring Adaptable Outputs 8 Wiring Pilot Water Heater Boiler Limit Breaker 9 Wiring Remote Shut Off 9 Auto Reset Buzzer Switches 9 Building Management System 10 Operation 10 Initial Power Up 10...

Page 3: ...ic medical conditions If in doubt consult a doctor physician Your product should reach you in perfect condition if you suspect it is damaged contact your supplier Warranty Statement Warranty Coverage...

Page 4: ...used for heating cooking and vehicles It is Obtained during the processing of crude oil or direct from the sea Colourless and odourless An odourising agent is added before distribution Half as heavy a...

Page 5: ...ted in positions determined by those who have knowledge of gas dispersion the process plant system and equipment involved and in consultation with both safety and electrical engineering personnel Take...

Page 6: ...electrical box Restrain the hazardous live wiring from accidental loosening to prevent wires from moving after installation and touching parts of opposite polarity or at low voltages Isolate the equi...

Page 7: ...than connected Heat detectors use wires suitable for at least 167 F 75 C Wiring Gas Solenoid Valve When the installation includes a standing pilot ensure the internal auto reset dip switch is in the O...

Page 8: ...iance Multiple appliance limit switches can be wired in series Wiring Adaptable Outputs The mini merlin can be used to effect external relays and contactors to disable multiple appliances when a fault...

Page 9: ...mally closed and will alarm when energised open isolating the gas supply When using this input only the mains utility output shall de energize If you are using the CO or NG relay to shut down a boiler...

Page 10: ...he touch sensor on the front cover for 3 seconds The detector enters a stabilisation phase for approximately one minute during this period the device is not operational If the detector has been config...

Page 11: ...h button is pressed and held during normal operation the mini merlin will simulate an open circuit to ensure all configured systems outputs alarms indications and other external devices operate as int...

Page 12: ...briefly exposing the unit to a known concentration of the target gas that usually exceeds the highest alarm point If the detector goes into alarm and all signals outputs activate then the system is w...

Page 13: ...ylinder All cylinders will re seal upon removal of the regulator valve Deviating from this test process is deemed improper and may affect the functional safety of your device Exposure to chemicals smo...

Page 14: ...ne LPG LEL Batch Cylinder No CO ppm Batch Cylinder No Propane LPG LEL Batch Cylinder No CO ppm Batch Cylinder No Propane LPG LEL Batch Cylinder No CO ppm Batch Cylinder No Propane LPG LEL Batch Cylind...

Page 15: ...3 15A 250Vac Equipment Overvoltage Category II Pollution Degree 2 Relays Volt Free BMS relay output 0 5A switching current resistive load Environmental Ingress Protection Not Formally Evaluated Opera...

Page 16: ...nded and is free from any unforeseen damage caused by transit installation Every effort is made to ensure the accuracy of this document however AGS can assume no responsibility for any errors or omiss...

Reviews: