GTI Grid Series

 

Installation instruction                                                                                                     

 

Figure 1 

 

1

Please read the below notes carefully before installation. 

  A) Make sure the open voltage and operation voltage is in the range of 10.5-28V, and we recommend 

the 18V rated voltage solar panel or 24V battery. 

 

B)  Make  sure  the  inverter’s  AC  voltage  and  frequency  is  the  same  with  power  grid  voltage  and 

frequency. 

  C)  Installation  inverter  in  the  low  humidity  and  well-ventilated  place  to  avoid  the  inverter  damp  and 

overheating, And clear the inflammable and explosive materials around. 

  D) Recommended to use 4AWG DC input cable that can handle more than 50A current. 

  E) DC input cable no more than 8M, because long DC cable will reduce the voltage from solar panel         

to inverter, then make some loss. 

  F)  There  must  be  a  circuit  breaker  between  solar  power  generation  and  power  grid(show  like  the   

“ switch    A” in figure 1). And there will be no load before the circuit breaker. 

  G) Before connect all the connections, you must  disconnect the utility power. After make sure the all       

connections are right then connect the utility power. 

  H) If you need to disconnect the mains switch when the solar power generation is in operation, you 

  must 

disconnect the control switch first(show like the “switch    A” in figure 1).   

  I)    Avoid children touch or play the inverters, in order to prevent electric shock. 

  J) Non-professional do not disassemble the inverter, only qualified serviceman can repair it. 

 

2

Connection DC terminal 

      Connect the solar panels positive terminal to inverter

’s positive terminal, and negative to negative. 

      And you must screw up the nut to avoid the bad contact.   

 

      Show in figure 2: 

 

Summary of Contents for 200W

Page 1: ... 1 GTI Grid Series 1 GTI Series Inverters For Grid User Manual ...

Page 2: ...uce different current output Use advanced CPU to operate the different illuminance and the data can be directly displayed on the LCD Then you can visually see the sense of the strength of the sun unit Used more convenient Power Automatically Locked APL In different current fluctuations we should use the MPPT function When the MPPT function adjusted to the maximum power point the product automatica...

Page 3: ...HDIAC 5 Phase 1 Islanding protection VAC f AC Output short circuit protection Current limiting Show LED Installation Wall hanging Cooling Fan Standby Power 1W Night Power 1W Ambient temperature range 25 60 Humidity 0 99 Indoor Type Design Waterproof Indoor Type Design Electromagnetic Compatibility EN50081 part1 EN50082 part1 Power System Disturbance EN61000 3 2 EN60950 1 Network test DIN VDE 1026 ...

Page 4: ...r panel to inverter then make some loss F There must be a circuit breaker between solar power generation and power grid show like the switch A in figure 1 And there will be no load before the circuit breaker G Before connect all the connections you must disconnect the utility power After make sure the all connections are right then connect the utility power H If you need to disconnect the mains sw...

Page 5: ...sure both of the terminal are connect fastness to avoid bad contact Show like figure 3 Figure 3 4 Operation After all connection first open the mains switch then open the inverter When the inverter s green LED shows it means the inverter start to work 5 Several or many inverters used in parallel In order to achieve higher power we can use this inverter in stack For example 4 pcs of 300W grid tie i...

Page 6: ... 6 GTI Grid Series 6 Show as figure 4 Figure 4 6 Single phase connection Connection electrical diagram of the solar inverter used in single phase power generation system show as below ...

Page 7: ... 7 GTI Grid Series 7 7 Three phase connection Connection electrical diagram of the micro inverter used in three phase generation system show below ...

Page 8: ...ge protection Input DC voltage is greater than 28 5VDC 3 Over temperature protection when the chassis temperature is above 75 the temperature dropped about 2 10 minutes to restart automatically after cooling 4 Fault Protection when 110VAC or 220VAC power outage or shutdown 5 Islanding protection When the electric supply stop the inverter automatically shut down output B Green LED 1 Green LED flash...