Turn-On Checkout
54
Checking the Current Function
ENERGY HAZARD
.
Some supplies (Series 668xA/669xA) can provide more than 240 VA at more
than 2 V. If the output connections touch, severe arcing may occur resulting in burns, ignition or
welding of parts. Do not attempt to make connections while the output is live.
The tests in Table 3-2 check the basic current functions with a short connected across the power supply output.
Do not
program maximum output currents unless the shorting wire is
capable of handling the current
(see "Supplemental
Characteristics" and Table 4-2). The
AMPS
display will show various readings. Ignore the
VOLTS
display.
Table 3-2. Checking the Current Functions (Output Terminals Shorted)
Action
Display
Explanation
Turn off the power supply
and connect a #14 AWG or larger wire across the output (+) and (-) terminals.
If you intend to
test at full-rated output current, use a wire or wires of sufficient size to carry the maximum current of the supply
(see "Supplemental Characteristics" in Chapter l and Table 4-2 in Chapter 4).
Turn on the supply.
Set the voltage to its maximum
value. This example assumes that
you have an 8-volt supply (see
"Performance Specifications" in
Chapter 1 for the value for your
specific supply) .
Meter mode
Essentially zero outputs with
Dis
annunciator on.
Press
VOLT 8.000
Program output to 8 volts.
Press
AMPS 1.000
Program output to 1 ampere.
CAUTION:
Be certain to observe this step with Series 668xA/669xA supplies. Start at
1 ampere before going to greater output currents.
Press
AMPS 1. 000
Dis
annunciator turns off,
CC
annunciator turns on, and
AMPS
display shows the programmed current.
Press
several times
*Current decreases several milliamperes each time you press the
key.:
Press
the same
number of times
*Current increases several milliamperes each time you press the
key.
*The number of milliamperes is determined by the current programming resolution of
the power supply (see "Supplemental Characteristics" in Chapter 1).
Rotate the
Current
control
first
counterclockwise and then
clockwise
Control operates similarly to the
and
keys.
The control is rate sensitive. Turning it more quickly causes a
more rapid change in current.
Press
You have enabled the overcurrent protection circuit. The circuit
then tripped because of the output short. The
CC
annunciator
turns off and the
OCP
and
Prot
annunciators come on. The
output current is near zero.
Summary of Contents for 6641A
Page 50: ......
Page 94: ......
Page 97: ...Calibration 97 Figure A 1 Calibration Test Setup c Series 668xA 669xA Setup ...
Page 106: ...Operation Verification 106 Figure B 1 Verification Test Setup c Series 668xA 669xA Setup ...
Page 118: ......
Page 128: ......
Page 136: ......