Installation 45
Table 3-2. Maximum Wire Lengths to Limit Voltage Drops
Wire Size
Resistivity
Maximum Length in Meters (Feet) to Limit
Voltage Drop to 0.5 V or Less
Cross
Section
AWG
Area in mm2
Ω
/kft
Ω
/km
5 A
10 A
20 A
30 A
40 A
50 A
60 A
22
16.15
(6)
(3)
(1.5)
(1)
(0.77)
(0.62)
(0.52)
0.5
40.1
2.5
1.2
0.6
0.4
0.31
0.25
0.21
20
10.16
(9.5)
(4.5)
(2)
(1.5)
(1.23)
(0.98)
(0.82)
0.75
26.7
3.7
1.9
0.9
0.6
0.47
0.37
0.31
18
6.388
(15.5)
(7.5)
(3.5)
(2.5)
(2.0)
(1.57)
(1.30)
1
20.0
5.0
2.5
1.3
0.8
0.63
0.50
0.42
16
4.018
(24.5)
(12)
(6)
(4)
(3.1)
(2.49)
(2.07)
1.5
13.7
7.3
3.6
1.8
1.2
0.91
0.73
0.61
14
2.526
(39.5)
(19.5)
(9.5)
(6.5)
(4.9)
(3.46)
(3.30)
2.5
8.21
12.2
6.1
3.0
2.0
1.52
1.22
1.01
12
1.589
(62.5)
(31)
(15.5)
(10.5)
(7.9)
(6.29)
(5.24)
4
5.09
19.6
9.8
4.9
3.3
2.46
1.96
1.64
10
0.9994
(100)
(50)
(25)
(17)
(12.5)
(10.00)
(8.34)
6
3.39
29
14.7
7.4
4.9
3.69
2.95
2.96
8
0.6285
(159)
(79)
(39.5)
(27)
(19.9)
(15.91)
(13.25)
10
1.95
51
25
12.8
8.5
6.41
5.13
4.27
6
0.3953
(252)
(126)
(63)
(40)
(31.6)
(25.30)
(21.07)
16
1.24
80
40
20
13.4
10.08
8.06
6.72
4
0.2486
(402)
(201)
(100)
(68)
(50.37)
(40.23)
(33.51)
Zero-Volt Loading Connections
As shown in Figure 3-15, the Electronic Load can be connected in series with a voltage source or auxiliary power supply
greater than 3 V so that the Electronic Load can test devices at its full current capacity down to a zero-volt level. Remote
sensing is recommended for improved load regulation and when turning the short on.
Summary of Contents for 6050A
Page 10: ......
Page 14: ......
Page 32: ......
Page 46: ...46 Installation Figure 3 12 Local Sensing Figure 3 13 Remote Sensing...
Page 47: ...Installation 47 Figure 3 14 Parallel Operation Figure 3 15 Zero Volt Loading...
Page 48: ......
Page 55: ...Local Operation 55 Figure 4 2 Recommended Programming Sequence...
Page 64: ......
Page 69: ...Remote Operation 69 Figure 5 1 Remote Programming Flowchart Sheet 1...
Page 70: ...70 Remote Operation Figure 5 1 Remote Programming Flowchart Sheet 2...
Page 74: ......
Page 78: ...78 Calibration Figure 6 2 Calibration Flowchart for A Modules...
Page 79: ...Calibration 79 Figure 6 2 Calibration Flowchart for A Modules continued...
Page 80: ...80 Calibration Figure 6 2 Calibration Flowchart for A Modules continued...
Page 85: ...Calibration 85 Figure 6 3 Calibration Flowchart for B Modules...
Page 86: ...86 Calibration Figure 6 3 Calibration Flowchart for B Modules continued...
Page 87: ...Calibration 87 Figure 6 3 Calibration Flowchart for B Modules continued...