To Disengage the Temperature Sensing Function:

1.  Remove the four screws on the alarm box and 

take the cover off.

2.  Remove Temperature Jumper from left/center 

pins and reinstall on right/center pins as 
shown in Image 7 (Fig. C).

3.  Replace the cover with the four screws.

NOTE: 

If the Temperature Jumper only utilizes two pins call or email AGF for 

instructions on how to engage/disengage the Temperature Sensing Function.

REMOTE NOTIFICATION FUNCTION

The Model 5100ALBV Water Detection Alarm also features a Remote Notification 
Function. This function allows you to connect the unit directly to the fire control 
panel or BMS, so when water is detected in the auxiliary drain you will be notified 
remotely.

Remote Operation Setup:

1.  Remove the four screws on the alarm box and 

take the cover off.

2.  Connect wiring to the Common Terminal and 

either the N.O. or N.C. terminal as shown in 
Image 8 (Fig. D). Contact is rated for 2.0A @ 
30VDC.

3.  Replace the cover with the four screws.

NOTE: 

Please call or email AGF for instructions on how to locally silence the 

audible alert if directly wire to a fire control panel or BMS.

+V

-V

COM

TEMPERATURE

JUMPER

VOLTAGE

JUMPER

N.O.

N.C.

Fig. C

Fig. D

Image 7

Image 8

•  Left/Center pins covered (TEMP -): 

Alarm functions at < 45° F (engaged)

•  Right/Center pins covered (TEMP +): 

Alarm functions at all times (disengaged)

TEMPERATURE

JUMPER

Summary of Contents for 5100ALBV

Page 1: ...INST 5100 5200 6 22 Models 5100ALBV 5100 5200 www agfmfg com Owner s Manual Owner s Manual Owner s Manual Owner s Manual Model 5100ALBV Model 5100A Model 5200A...

Page 2: ...LECTanDRAIN Models 5100 and 5200 are NOT designed to prevent freezing or automatically drain condensation from the system FAILURE TO DRAIN CONDENSATION MAY RESULT IN CATASTROPHIC SYSTEM FAILURE DUE TO...

Page 3: ...FPA 13 standards pertaining to low point drains auxiliary drains 2 Confirm that the supply valve upper is in the open position and ready to collect condensation the drain valve lower is closed and the...

Page 4: ...NSTRUCTIONS The Model 5100ALBV Water Detector operates on the principle of conductivity It contains a probe that is attached to the piping system and when condensate collects in the piping and reaches...

Page 5: ...ately for this and any other loads on the same circuit Battery Operation 1 Remove the four screws on the alarm box and take the cover off 2 For battery operation check to make sure the Voltage Jumper...

Page 6: ...g B Ensure DC is from a clean power supply and not full wave rectified without a capacitor 6 Replace the cover with the four screws TEMPERATURE SENSING FUNCTION When the Temperature Sensing Function i...

Page 7: ...Alarm also features a Remote Notification Function This function allows you to connect the unit directly to the fire control panel or BMS so when water is detected in the auxiliary drain you will be...

Page 8: ...AGF Manufacturing 100 Quaker Lane Malvern PA 19355 Phone 610 240 4900 techsupport agfmfg com www agfmfg com...

Reviews: