To Disengage the Temperature Sensing Function:
1. Remove the four screws on the alarm box and
take the cover off.
2. Remove Temperature Jumper from left/center
pins and reinstall on right/center pins as
shown in Image 7 (Fig. C).
3. Replace the cover with the four screws.
NOTE:
If the Temperature Jumper only utilizes two pins call or email AGF for
instructions on how to engage/disengage the Temperature Sensing Function.
REMOTE NOTIFICATION FUNCTION
The Model 5100ALBV Water Detection Alarm also features a Remote Notification
Function. This function allows you to connect the unit directly to the fire control
panel or BMS, so when water is detected in the auxiliary drain you will be notified
remotely.
Remote Operation Setup:
1. Remove the four screws on the alarm box and
take the cover off.
2. Connect wiring to the Common Terminal and
either the N.O. or N.C. terminal as shown in
Image 8 (Fig. D). Contact is rated for 2.0A @
30VDC.
3. Replace the cover with the four screws.
NOTE:
Please call or email AGF for instructions on how to locally silence the
audible alert if directly wire to a fire control panel or BMS.
+V
-V
COM
TEMPERATURE
JUMPER
VOLTAGE
JUMPER
N.O.
N.C.
Fig. C
Fig. D
Image 7
Image 8
• Left/Center pins covered (TEMP -):
Alarm functions at < 45° F (engaged)
• Right/Center pins covered (TEMP +):
Alarm functions at all times (disengaged)
TEMPERATURE
JUMPER