External Hard Wire Operation:

1.  Remove the four screws on the alarm box and 

take the cover off.

2.  For external power operation, place the 

Voltage Jumper on the two rear pins as 
shown in Image 4 (Fig. B).

3.  While supporting the bottom of the alarm 

enclosure remove the knockout using a 
slotted screwdriver and a hammer (place a 
clean rag underneath the knockout to prevent 
debris from falling onto the circuit board).

4.  Install ½”, watertight conduit fitting or cord 

grip into the knockout opening and run the 
external power source into the alarm housing 
as shown in Image 5.

5.  Connect external power source to V+ and V- 

terminals as shown in Image 6 (Fig. B). Ensure 
DC is from a clean power supply and not full-
wave rectified without a capacitor.

6.  Replace the cover with the four screws.

TEMPERATURE SENSING FUNCTION

When the Temperature Sensing Function is enabled and water is present in the 
auxiliary drain the Model 5100ALBV will not activate the audible and visual alerts 
if the ambient temperature is above 45° F. When water is present and the ambient 
temperature falls below 45° F the Model 5100ALBV will activate the audible and 
visual alerts. The Temperature Sensing Function helps extend battery life and 
eliminates unwanted alarm conditions when the threat of freezing is not present. 

By default, the Temperature Sensing Function is enable when shipped. The 
Model 5100ALBV will not detect water unless the temperature is under 45° F.

 

See page 7 to disengage Temperature Sensing Function.

+V

-V

COM

TEMPERATURE

JUMPER

VOLTAGE

JUMPER

N.O.

N.C.

Fig. B

VOLTAGE

JUMPER

Image 4

Image 5

Image 6

Summary of Contents for 5100ALBV

Page 1: ...INST 5100 5200 6 22 Models 5100ALBV 5100 5200 www agfmfg com Owner s Manual Owner s Manual Owner s Manual Owner s Manual Model 5100ALBV Model 5100A Model 5200A...

Page 2: ...LECTanDRAIN Models 5100 and 5200 are NOT designed to prevent freezing or automatically drain condensation from the system FAILURE TO DRAIN CONDENSATION MAY RESULT IN CATASTROPHIC SYSTEM FAILURE DUE TO...

Page 3: ...FPA 13 standards pertaining to low point drains auxiliary drains 2 Confirm that the supply valve upper is in the open position and ready to collect condensation the drain valve lower is closed and the...

Page 4: ...NSTRUCTIONS The Model 5100ALBV Water Detector operates on the principle of conductivity It contains a probe that is attached to the piping system and when condensate collects in the piping and reaches...

Page 5: ...ately for this and any other loads on the same circuit Battery Operation 1 Remove the four screws on the alarm box and take the cover off 2 For battery operation check to make sure the Voltage Jumper...

Page 6: ...g B Ensure DC is from a clean power supply and not full wave rectified without a capacitor 6 Replace the cover with the four screws TEMPERATURE SENSING FUNCTION When the Temperature Sensing Function i...

Page 7: ...Alarm also features a Remote Notification Function This function allows you to connect the unit directly to the fire control panel or BMS so when water is detected in the auxiliary drain you will be...

Page 8: ...AGF Manufacturing 100 Quaker Lane Malvern PA 19355 Phone 610 240 4900 techsupport agfmfg com www agfmfg com...

Reviews: