Normally, Pro3-XP frames are shipped with the plates installed.    As a result the press and plates 

can  weigh  several  thousand  pounds.    We  recommend  only  qualified  forklift  operators  should  lift  and 
position the unit.  It should be noted that the high leg frame, also known as the Pro3-XPH, can be top heavy 
and could tip if they are not moved properly.  

Drawing Package: 

Every  frame  is  shipped  with  a  drawing  package.    This  drawing  package  contains  important 

information that is specific to your heat exchanger.  If you cannot find the drawing package, contact AGC 
Heat Transfer or your local AGC distributor to obtain a replacement prior to installing the heat exchanger.  

The drawing package is a collection of several important documents related explicitly to your heat 

exchanger.  The first of these is the streaming diagram.  Two copies of the streaming diagram are included.  
One copy has been laminated to protect it.  This copy is intended to be used by production and maintenance 
personnel when installing and/or servicing the heat exchanger. The remaining copy should be kept on file 
in a safe place in the event the production copy is lost or damaged.  The streaming diagram (also referred 
to as the drawing) describes all the characteristics of the heat exchanger.  Figure 2 shows a typical two page 
streaming diagram

.  

Figure 2 

Typical Streaming Diagram

 

Page one shows the unit serial number, the duty, plate type, plate count, gasket type, connection 

type, connection size, and the tightening dimension.  Revisions are also listed on page one.  Page two of 
the drawing shows how the fluids pass through the heat exchanger.  (The ProFlow manual describes how 
to read this flow diagram).  If the unit is small, such as the unit in figure two, a front and side view of the 
heat exchanger will be shown as well.  For larger units the front and side views are shown on page three or 
page four.    

The second document in the drawing package is a plate punching diagram.  This diagram will show 

you how to identify each Pro3 plate either by its configuration number (stamped at the top of each plate) or 
by looking at the plate noting which ports have been opened.  Since the Pro3 plate is a vertical flow plate, 
each plate can be used for either a right or left hand plate.  The ProFlow manual explains how these plates 
are used in greater detail.  

Summary of Contents for ProFlow Pro3-XP

Page 1: ...AGC Model Pro3 XP Operation and Maintenance Manual...

Page 2: ......

Page 3: ...ro3 XP Rail Size Chart 11 Pro3 XP Tiebolt Assembly 12 Pro3 XP Terminal Assembly 13 Pro3 Plate and Frame Gaskets 14 www agcheattransfer com Western 3109 NE 230th Avenue Fairview OR 97024 1 503 774 7342...

Page 4: ......

Page 5: ...recommendations could result in injury to the operator or cause damage to the heat exchanger Receiving and Inspection Each AGC heat exchanger is assembled and fully tested at the factory prior to shi...

Page 6: ...should be kept on file in a safe place in the event the production copy is lost or damaged The streaming diagram also referred to as the drawing describes all the characteristics of the heat exchange...

Page 7: ...y lift the press off the skid The top rail can be used as a lifting point Never lift the press by the tiebolts These bolts are in slots and are not designed to support the weight of the frame for lift...

Page 8: ...ng the ball feet to establish a slope from end to end Figure 5 shows a press adjusted to drain forward to the fixed end Figure 5 Frame Adjusted to Drain to Fixed End Consult your onsite Plant Engineer...

Page 9: ...ion include enough breaks in the piping so service and maintenance can be completed easily The piping connected to the follower should be configured with joints that are easy to remove so the follower...

Page 10: ...shipped in a separate crate refer to the ProFlow manual for instructions on installing them Figure 7 Tightening Instructions Most new plate packs will seal at the start dimension As the plates and gas...

Page 11: ...press is closed and all connections are made to the heat exchanger the unit is ready to be pressure checked Consult the onsite plant engineer or project manager for the correct procedure on pressure t...

Page 12: ...Heat Transfer heat exchangers are designed to require minimal operator maintenance As long as the unit is operated within the pressure and temperature limits the only maintenance required is routine...

Page 13: ...s Most of the field replaceable parts are listed in this manual If the part you need is not listed on the following pages contact your local AGC distributor or the AGC Heat Transfer Factory Contact in...

Page 14: ...hers unless specifically ordered Item Quantity Part Number Description 1 1 11012310 Pro3 XP Fixed End 2 1 See Chart Pro3 XP Upper Rail 3 1 See Chart Pro3 XP Bottom Rail 4 1 11012330 Pro3 XP Follower 5...

Page 15: ...ail Size Rail Length Upper Rail Part Number Lower Rail Part Number 1 1118 44 11012365 11014700 2 1701 67 11012366 11014703 3 2311 92 11012367 11014704 4 2921 115 11012368 11014705 Pro3 XP Rail Size Ch...

Page 16: ...2377 Pro3 XP Tie Bolt Bushing Pro3 XP Tie Bolt Size Chart Tie Bolt Size Overall Length Tie Bolt Base Part Number Complete Assembly Number 1 1118 44 11012374 11012370 2 1701 67 11012375 11012371 3 2311...

Page 17: ...335 Pro3 Port Boss V Configuration 11018516 Pro3 Port Boss X Configuration 11018515 Pro3 Port Boss with 2 Pressure Switch 11018518 Pro3 Port Boss Blank 11018520 Pro3 Port Boss Thru 11018513 Note Port...

Page 18: ...14 Pro3 Plate and Frame Gaskets...

Page 19: ......

Page 20: ...packs gaskets and spares that fit other brands Frames available are tie bolt twin spindle and hydraulic automatic closure AGC offers Platecheck TM Field Leak Testing of plate heat exchangers that meet...

Reviews: