20
AGA Ellesmere Standard Gas Stove
3. Installation Instructions.
Before commencing Installation, confirm that the details on the appliance data plate correspond to the
local distribution conditions, gas type and pressure to which the appliance is to be installed.
Ensure that gas supply and supply pipe is capable of delivering the required volume and pressure of gas
and is in accordance with the rules in force.
3.1 Gas Connection
This appliance has a gas inlet connection of Ø 8mm.
You must fit an isolation tap with a pressure
test point incorporated into it at the rear or the side of the stove so the gas supply can be easily
isolated if required
3.2 Ventilation
This appliance is a Balanced Flue room sealed appliance, and as such needs no additional ventilation.
However an adequate supply of fresh air to maintain temperatures and a comfortable environment is
recommended.
This appliance may be installed in a completely sealed or mechanically ventilated house.
3.3 Appliance Free-standing Installation
Determine the position required for the appliance.
Create a gas connection with
ON/OFF TAP
for the appliance in approximately the correct location for
the gas controls.
The gas controls are connected to the Burner of the appliance. (Factory Fitted)
Do not make any adjustments to the appliance.
The Flue system should be fitted with a minimum clearance of 350mm from any combustible objects or
materials; this includes any combustible materials used for the fireplace construction.
As this is a room sealed appliance and the appliance stands appropriately and is securely fixed to the
floor, a hearth is not required for this appliance. But a hearth would be a requirement when being fitted
to a combustible floor surface such a carpet, wooden or laminate flooring
A minimal gap of 100mm should be left all round the appliance to non-combustible materials.
For minimum clearance to combustible materials see table overleaf
– However any installation must be
in accordance with the latest Local Building Regulations