10
Product description
EN
PrimoTherm® Floor
4.4
Function
Safety temperature cut out
The surface mounting thermostat is used as a safety temperature cut out.
The circulation pump automatically switches off if a safety-related tempera-
ture limitation is exceeded.
The safety-related temperature limitation is adjustable within a range from
20 to 60 °C. The temperature factory setting is 55 °C.
Operating modes circulation pump
The circulation pump features the following operating modes:
•
Constant volume flow
•
Constant pressure
•
Venting function of pump housing
The product is a pump
assembly for constant control
of the flow temperature of
water-based surface heating
systems. With the integrated
thermostatic mixing valve,
the flow temperature can be
adjusted to the desired tem-
perature by adding water
from the return.
The vent screw and the
enclosed vent screw allow
you to vent the entire surface
heating/cooling system.
The product is suitable for
most standard manifold sys-
tems.