Fault codes and the responses to them
Supply water sensor failure
· Push Enter (C) briefly to open the quick menu and check temperature T1.
· If the value is +99.9 degrees, there is no communication between the supply water sensor and the
motor unit.
- cable failure or connector disconnected » inspect
- if there is no mechanical failure » replace the supply water sensor
· If the supply water temperature is below zero (-01.4 C) = short-circuit in the sensor circuit.
- cable short-circuit » inspect the cable
- if there is no mechanical failure » the supply water sensor needs to be replaced
RF transmitter failure
· Take the room unit to the motor unit.
· Check that the RF transmitter is connected and that the cable is not damaged.
· Disconnect the power from the motor unit and then briefly remove one battery from the room unit.
· If the function is restored to normal when power is reconnected, return the room unit to its place after
pushing the setup button (D) and selecting “RF”.
· Let the unit calculate the average radio communication value for a while. If the value is below 30%,
check if you can improve signal strength by relocating the room unit nearby.
· The location of the RF transmitter can also affect the range of radio communication significantly »
always locate the RF transmitter as high as possible and away from power cables.
EN
32
33
Summary of Contents for AM20 SW 1.16
Page 2: ...1 2 D C B A 2 ...
Page 16: ...Symbole dolnego rzędu menu użytkownika menu ustawień tryb ECO tryb HOLIDAY 16 ...
Page 20: ...In English Setup and User Guide for AFRISO BWR Heating Controller AM20 SW 1 16 RU SW 1 18 20 ...
Page 32: ...Bottom row symbols user menu setup menu ECO mode HOLIDAY mode 32 ...
Page 48: ...Символы нижнего ряда меню пользователя Меню настроек режим ECO режим ОТПУСК 48 ...
Page 52: ...3 2016 AFRISO Sp z o o Szałsza ul Kościelna 7 42 677 Czekanów zok afriso pl www afriso pl ...