23
Mounting
EN
RG 210
5.3.1
Power supply
Verify that the power supply to the control unit can be switched off and
is equipped with a separate fuse (16 A maximum).
1. Connect the control unit to mains by means of a permanently installed
cable, for example NYM-J 3 x 1.5 mm².
2. Route the mains cable through the upper rubber cable gland into the
black base of the control unit.
3. Connect the phase to terminal
L1
.
4. Connect the neutral conductor to terminal
N
.
5. Connect the protective conductor to terminal
PE
.
5.3.2
Probe
1. The probe cable(s) require(s) permanent installation.
- Standard shielded cable 2 x 0.5 mm
2
can be used to extend the probe
cable. The maximum length of the extension cable is 50 m.
2. Route the probe cable through the bottom rubber piece(s) of the black
base.
3. Connect the probe cable(s) to the appropriate terminal(s) with the
designation "Probe 1"/"Probe 2".
- You do not have to ensure a specific polarity.
NOTICE
INTERFERENCE
•
Verify that the probe cable is not routed next to or in parallel with cables car-
rying mains voltage.
•
Verify that the probe cable is sufficiently protected from damage, for example
by installing it in a metal pipe.
Failure to follow these instructions can result in equipment damage.
Summary of Contents for 53206
Page 10: ...10 Produktbeschreibung DE RG 210 C Sockel D Gehäuseoberteil Abbildung 1 Signalteil C D ...
Page 12: ...12 Produktbeschreibung DE RG 210 4 3 Abmessungen 113 mm 53 mm ...
Page 42: ...10 Product description EN RG 210 C Base D Upper part of housing Fig 1 Control unit C D ...
Page 44: ...12 Product description EN RG 210 4 3 Dimensions 113 mm 53 mm ...
Page 76: ...12 Description du produit FR RG 210 4 3 Dimensions 113 mm 53 mm ...