VESTA  80  dehumidifiers  are  utilised  for  summer 

dehumidification  of  rooms  with  radiant  panel  cooling 

systems. 

VESTA 80 is designed and built exclusively for indoor 

installation.  Outdoor  installation  of  the  unit  is  strictly 

prohibited.

The appliance is available in three versions:

VESTA 80 

FVI

 - Vertical recessed exposed unit

The dehumidifier is recessed into the wall utilising a

wood frame.

VESTA 80 

HI

- Horizontal ductable unit

In this configuration the airflow at the outlet can be

routed directly into a duct and then diffused into the

room through an outlet vent.

 

In  the  VESTA  80

HI

  versions  the  ducts, 

vents  (intake  and  outlet)  and  room  air  intake 

filter 

must be supplied by the installer.

The structure is made of galvanized steel sheet. The 

fan unit is composed of a centrifugal fan with six-speed 

motor  that  assures  high  performance,  efficiency, and 

low noise operation.

Air treatment is provided by a refrigerant circuit 

composed of pre and post-treatment coils made 

of  copper  tube  with  aluminium  fins, a  reciprocating 

compressor mounted on antivibration supports 

or 

springs  (VESTA 80V ), a capillary expansion tube 

and a filter-dryer.

VESTA  80  delivers  air  at  neutral  temperature  with 

respect to the room air. This characteristic is assured 

by the presence in the unit of a post-cooling coil through 

which  water  from  the  radiant  panels  system  can  be 

circulated.

VESTA 80 is controlled by the regulation and control 

system, also when several units are installed in parallel.

Optimal installation for all types of system is guaranteed 

by a range of optional accessories.

1

2

11

3

4

5

6

7

8

9

10

1 Centrifugal fan

2 Sheet steel structural frame

3 Air treatment coils assembly
4

Condensate drain (rubber hose with inside Ø 

of 15 mm)

5 Stainless steel condensate collection tray
6

Union for pre and post-treatment coil: 3/8” GAS 

female (WATER INLET)

VESTA 80 

FVI

 - vertical recessed exposed version

7

Union for pre and post-treatment coil: 3/8” GAS 

female (WATER OUTLET)

8

Electrical junction box: connections for power 

input and unit control circuit

9 Compressor

10 Acoustically insulated compressor compartment

11 Air bleed valve for pre and post-treatment coils

Front view

Side view

APPLIANCE DESCRIPTION

3

Summary of Contents for VESTA 80 FVI

Page 1: ...VESTA 80 series Isothermal dehumidifiers VESTA 80 FVI Vertical version for exposed recessed VESTA 80 HI Horizontal ductable version INSTRUCTION OPERATING AND MAINTENANCE MANUAL MIU VE80I GB 002 05 17...

Page 2: ...s appear in this handbook Warning Prohibited I Installer U User A Technical Support Compliance and range 1 Precautions 2 Safety prescriptions 2 Appliance description 3 Identification 4 Technical data...

Page 3: ...magnetic compatibility Directive 2014 30 EU Standards Safety machinery electrical equipment of machines Part 1 General requirements EN 60204 1 2006 and rev EN 55014 1 2006 Electromagnetic compatibilit...

Page 4: ...d by the manufacturer and insist on the use of genuine original replacement parts Failure to comply with the above prescriptions will impact negatively on the safety of the appliance Do not use extens...

Page 5: ...minium fins a reciprocating compressor mounted on antivibration supports or springs VESTA 80V a capillary expansion tube and a filter dryer VESTA 80 delivers air at neutral temperature with respect to...

Page 6: ...porator con denser post treatment 9 Fan access panel 10 Compressor VESTA 80 HI horizontal ductable version Top view with internal layout of the main unit components Side view water and condensate drai...

Page 7: ...5x201x695 mm Frame WxDxH 750x230x740 mm Version VESTA 80 HI WxDxH mm Pre and post treatment coils hydraulic connections VESTA 80 FVI no 2 3 8 GAS female Version VESTA 80 HI no 2 1 2 GAS female Total s...

Page 8: ...essure of the fan The speed regulating system of the fan allows the balance of the pressure drop which is due to the different lengths of the ducts VESTA80I is equipped with refrigerating system with...

Page 9: ...I U A ELECTRICAL DIAGRAM REFRIGERANT CIRCUIT 7...

Page 10: ...struction handbook is an integral part of the appliance Please read it carefully and keep it safe Remove the packing material only when the unit has been moved to the point of installation It is prohi...

Page 11: ...y the system designer or a suitably skilled technician and must take account of technical requirements technical standards and compliance with statutory legislation VESTA 80 HI Horizontal ductable ver...

Page 12: ...the frame into the recess Clean the recess carefully before inserting the frame Before routing the various pipes into the dehumi difier installation recess fit the frame in such a way as to be able to...

Page 13: ...draulic pipes and electrical wiring Front panel Clearance 60 mm Attach the front panel as shown in the figure 11 25 mm 25 mm 30 mm 30 mm Side view panel panel Top view VESTA 80 FVI VESTA 80 FVII Diagr...

Page 14: ...technician and must take account of technical requirements technical standards and compliance with statuto ry legislation Check pressure drops of the air outlet intake gril les and any ducts in relat...

Page 15: ...t is perfectly level or slightly tilted in such a way as to facilitate the drainage of condensate through the metal manifold Suspended from ceiling side view The figure alongside shows two methods of...

Page 16: ...ompressor access panel 4 Removable cover 5 Electrical panel Mounted on beams The figure alongside shows installation of the appliance on a flat surface Choose antivibration mounts in compliance with t...

Page 17: ...ifold and siphon Condensate drain VESTA 80 dehumidifiers are equipped with a condensate collection tray to be connected to a drain hose that must be routed to a suitable drainage point VESTA 80 FVI VE...

Page 18: ...he electrical circuit diagrams Model Power supply V Ph Hz Max power consumption W Max current input W Delayed action line fuse A Power input con ductor cross section mm2 Earth conductor cross section...

Page 19: ...uit must be emptied or it must protected by adding antifreeze such as ethylene glycol in the amounts recommended by the antifreeze producer CHECKS DURING AND FOLLOWING COMMISSIONING PROLONGED DISUSE O...

Page 20: ...ore changing the fan speed DISCONNECT THE MAINS SUPPLY to the appliance 3 is Minimum speed for plastic and metal fan is Red 2 is Medium speed default for metal fan is Orange for Metal fan is Blue 1 is...

Page 21: ...hen water starts to flow from the appliance bleed valves close them and continue filling up to the pressure value specified for the system Check that the hydraulic unions are watertight This operation...

Page 22: ...Operation without the panels cor rectly fitted can lead to malfunctioning of the unit poor efficiency difficulty in draining condensate with consequent dripping water from the unit Before starting up...

Page 23: ...pplied with the room control panel you are using OPERATIONS POSSIBLE ON THE ROOM CONTROL PANEL Accessory Activation Set the main switch to On Set the required room humidity value by means of the regul...

Page 24: ...hat the VESTA 80 unit is effectively con nected to the electrical supply For all communications requests for technical service or replacement parts always quote mod el and serial number shown on the i...

Page 25: ...s are composed of a series of flashes having the following meaning If the VESTA 80 appliance is to be scrapped it must be disassembled and the parts sorted according to their construction material by...

Page 26: ...NOTES 24...

Page 27: ......

Page 28: ......

Reviews: