18
Mod. WRL
U.M.
200
400
500
System side heat exchanger (Evaporator)
Min. flow rate
gpm
11.89
11.89
36.10
Max. flow rate
gpm
73.97
73.97
211.34
Source side heat exchanger (Condenser)
Min. flow rate
gpm
12.77
12.77
41.83
Max. flow rate
gpm
73.97
73.97
211.34
Minimum water operating pressure (PN)
psi
7,3
7,3
7,3
Maximun water operating pressure (PN)
psi
116,0
116,0
116,0
Mod. WRL-H
U.M.
200
400
500
System side heat exchanger (Evaporator)
Min. flow rate
gpm
11.89
11.89
41.83
Max. flow rate
gpm
73.97
73.97
211.34
Source side heat exchanger (Condenser)
Min. flow rate
gpm
11.89
11.89
41.83
Max. flow rate
gpm
73.97
73.97
211.34
Minimum water operating pressure (PN)
psi
7,3
7,3
7,3
Maximun water operating pressure (PN)
psi
116,0
116,0
116,0
Reference data in cooling operation
Evaporator:
Water temperature (in/out) 54.0/44.1 °F
Condenser:
Water temperature (in/out) 84.9/94.6 °F
Reference data in cooling operation
Evaporator:
Water temperature (in/out) 54.0/44.1 °F
Condenser:
Water temperature (in/out) 84.9/94.6 °F
Reference data in heating operation
Evaporator:
Water temperature (in/out)
50/41 °F
Condenser:
Water temperature (in/out)
104/113 °F
STANDARD RATINGS
HEAT PUMP WATER SIDE INVERSION [ ° ]
(no pump version)
HEAT PUMP REFRIGERANT SIDE INVERSION [ H ]
(no pump version)