background image

25

extra low voltage (24V~ ) use this voltage also for energising the valves 
(terminals 2, 3 and 4), thus using 24V~ powered valves, in order not to 
jeopardize the safety of the installation with unsafe voltages.
In case the thermostat is powered with 230V~ use 230V~valves.

In case of 230V~ mains power it is mandatory to respect Live and 
Neutral indication.

At terminal 7 an input for remote heating/cooling selection is made 
available. In case this function is not used, the same terminal input can be 
used to activate the ‘Economy’ mode.
A remote temperature sensor can be wired to terminals 13 and 14. 
The selection between internal or remote sensor is made through the 
configuration procedure.
Terminals 12 and 14 feature a further input to which several types of 
sensor can be wired in order to accomplish special functions: the user can 
wire a supply water temperature sensor for performing the ‘changeover’ 
and/or ‘cu-toff thermostat’; as an alternative a bimetallic thermostat can 
be wired here, still for a ‘cut-off thermostat’ function; further a window 
contact can be wired.

Note: some limitations exist for the window contact: please read 
carefully the ‘WARNING’ section.

The preferred sensor type can be set in the configuration menu. 
The fan is controlled in a continuous proportional way. It is necessary to 
connect a drive suitable to accept a 0..10V input signal and control the fan 
motor at the output.
The proportional output of the fan at terminal 9 and the reference earth at 
terminal 8 shall control the drive input, as shown in figure 5 and 6. 
The input signal earth is often internally connected to the supply Neutral. 
In this case, it is possible not to connect the terminal 8 (output signal 
earth) because the earth is granted by the Neutral supply terminal (take 
care this Neutral is connected to terminal 6).
Should the thermostat be supplied with 24V~ , such a low voltage may 
be connected to the 230V~ Neutral through the motor drive. In this case, 
you cannot consider the 24V~ as a very low safety voltage: hence, it will 

be the installer’s duty to grant a proper insulation.
The device can control either one or two ON/OFF actuators, type NC or 
NO. The heat output is at terminal 2. The cool output is at terminal 3. On a 
2-pipe unit, just one valve is used both for heat and cool. In this case, the 
control signal will be the heat signal at terminal 2.

Read carefully also the paragraph “WARNING”.

TECHNICAL FEATURES

Power supply: 

230V~ -15% +10% 50Hz or

 

24V~ -15% +10% 50Hz

Power absorption: 

1,2W

Room temperature
 

Regulation range: 

5.0 .. 35.0 °C (configurable)

 

Sensor type: 

NTC 4.7kΩ @ 25°C ±2%

 

Precision: 

± 1.0 °C

   

Resolution: 

0.1 °C

 

Display temp. range: 

0.0 .. 40.0 °C

Supply pipe temperature
 

Sensor type: 

NTC 4,7kΩ @ 25°C ±2%

 Precision: 

± 

°C in the 20 .. 50 °C range

 Resolution: 

°C

 

Display temp. range: 

0 .. 99 °C

 Differential: 

°C

ON/OFF actuator outputs
 

Contact capacity: 

3A @ 250V~ cos

φ

=1

Proportional outputs
 

Signal range: 

0..10 V

 

Signal precision: 

±0.26 V

 Minimum 

actuator

 impedance: 

2,7 

KOhm

Regulation
 

Proportional band: 

0.8 .. 8.0 °C

ENGLISH

ESPAÑOL

DEUTSCH

ITALIANO

FRANÇAIS

Summary of Contents for WMT20

Page 1: ...ND 0 10V OUTPUT THERMOSTAT MIT BILDSCHIRM FÜR FAN COIL MIT AUSGANG FÜR VENTILATOR 0 10V THERMOSTAT AVEC ECRAN POUR VENTILO CONVECTEURS ET SORTIE VENTILATEUR 0 10V TERMOSTATO CON DISPLAY PARA FAN COIL CON SALIDA VENTILADOR 0 10V WMT20 37040 Bevilacqua VR Italia Via Roma 996 1103 AWMT20UJ 6371600_04 ...

Page 2: ...dukten und Dienstleistungen vorzunehmen Der Hersteller haftet für die Produktkonformität gemäß der Europäischen Richtlinie 1999 44 EG und dem Dokument zur Produktgarantiepolitik der Hersteller Auf Anfrage steht Ihnen beim Händler der ausführliche Produktgarantietext zur Verfügung GARANTÍA En la óptica de un continuo desarrollo de los propios productos el fabricante se reserva el derecho de aportar...

Page 3: ...3 INSTALLAZIONE INSTALLATION AUFSTELLUNG INSTALLATION INSTALLACIÓN Fig 4 Abb 4 2 1 Fig 2 Abb 2 Fig 1 Abb 1 B B A JP1 JP2 JP3 14 12 13 9 8 2 7 6 5 4 3 Fig 3 Abb 3 ...

Page 4: ...lador Bild 5 Verbindungsschema für die Steuerung der beiden Aktuatoren on off mit 230V pro Anlage mit 4 Rohren und proportionaler Steuerung SCHEMA DI COLLEGAMENTO WIRING DIAGRAM SCHALTSCHEMA SCHÉMA DE BRANCHEMENT ESQUEMA DE CONEXIÓN V FAN Uscita segnale 0 10V ventilatore 0 10V fan signal output Signalausgang 0 10V Ventilator Sortie signal 0 10V ventilateur Salida señal 0 10V ventilador SWI Sonda a...

Page 5: ...nnected to the 230V Neutral through the motor drive In this case you cannot consider the 24V as a very low safety voltage hence it will be the installer s duty to grant a proper insulation aACHTUNG Im Falle einer Anspeisung des Thermostats von 24V kann man diese Niedrigspannung an den Neutralpunkt von 230V mithilfe der Betätigung des Motors anschließen In diesem Fall kann man bei 24V nicht mehr vo...

Page 6: ... The fan proportional output is always turned off 0V when the valve output OUT COOL or OUT HEAT is off not shown on the scheme Le schéma montre le pilotage des vannes dans un système à 4 tuyaux avec zone neutre De façon analogue la sortie de la vanne chaude OUT HEAT d un système à 2 tuyaux sera pilotée de la même manière dans ce cas là la Ts température du point de consigne coïncidera avec la Ts r...

Page 7: ... ON OFF válvula calor V FAN Uscita proporzionale ventilatore Fan proportional output Proportionaler Ausgang Ventilator Sortie proportionnelle du ventilateur Salida proporcional ventilador Ta Temperatura ambiente Ambient temperature Umgebungstemperatur Température ambiante Temperatura ambiente Ts Temperatura setpoint manopola Setpoint temperature knob Temperatur Setpoint Einstellgriff Température d...

Page 8: ...8 Fig 8 2 BUUFOUJPO GPS 3 QJQF G 5BU ...

Page 9: ...9 Fig 9 ...

Page 10: ...10 Fig 10 ...

Page 11: ...Normal When changing the readout the controller informs the user about the parameter shown according to the following table tA Room ambient temperature Set Set point temperature TP Supply pipe water temperature ECO Economy function Active When the button is depressed several times the display readout cycles across the above mentioned temperatures After a few inactivity seconds the display readout ...

Page 12: ...stic cover pressing with the help of a tool like a screwdriver the plastic tooth located in the lower slot as indicated in Fig 1 raising at the same time the front cover as indicated in Fig 2 2 Unmount the plate fixed at the controller back by pressing the plastic tooth shown in A Fig 3 and at the same time pull the plate to the bottom until it becomes free from the plastic base 3 Fix the plate to ...

Page 13: ...rtional output of the fan at terminal 9 and the reference earth at terminal 8 shall control the drive input as shown in figure 5 and 6 The input signal earth is often internally connected to the supply Neutral In this case it is possible not to connect the terminal 8 output signal earth because the earth is granted by the Neutral supply terminal take care this Neutral is connected to terminal 6 Sho...

Page 14: ...e than one controller is not allowed All remote sensors bimetallic contact and window contact must have a galvanic insulation against earth as well as against the mains power In case precending two directions are not respected an irreversible product damage can follow All remote sensors bimetallic contact and window contact must be double insulation or reinforced insulation rated in case they are ...

Page 15: ... sensor and can be displayed with 1 C resolution in the 0 99 C range In case the acquired temperature falls outside the operating range mentioned the display will show the letters Or out of range In case the sensor acts as an open circuit or a short circuit the display will show the letters EEE error and all functions related with this data are not performed In case the system doesn t require the ...

Page 16: ...leaned In order to reset the warning and the relevant time counter once the cleaning has been made just keep depressed the speed button for at least 10 seconds until the regulator will confirm to have reset the warning by showing again the words FIL TER Temperature regulation This device can drive in a proportional way the fan speed in order to control room temperature with the highest comfort and ...

Page 17: ...he actual parameter allowable range In order to disable the access to configuration menu to unauthorized users an internal jumper JP3 shown in Fig 3 can be removed after this any attempt to enter in the configuration menu will result in an error message Configuration parameters explanation All parameters used in the installer configuration are shown in Table 1 and explained in the following P01 System...

Page 18: ... on P08 This parameter sets the type of sensor connected to the supply water temperature input at terminals 12 and 14 When set to value 0 or 1 a temperature sensor is expected for the acquisition of water temperature When 1 is set the temperature value is also shown over the display according to the user choice In case 0 is set the information coming from the temperature sensor is still used for t...

Page 19: ... raised when in cooling mode by this step once the Economy function is made active When this is set at 0 0 the Economy function is actually disabled P19 This parameter defines the hysteresis in C with which the ON OFF outputs are controlled according to the ambient temperature variations P20 In case the controller is configured for a neutral zone operation this parameter determines the relevant ampl...

Page 20: ... same duct for signal wires and power wires as the temperature reading accuracy could be impaired Wirings can be usefully made with bipolar screened cable whose screen is only wired at the regulator side terminal 14 with 1 5 mm minimum cross section and 15 m maximum length In the normal operation with internal sensor the controller conditions the signal acquired according an exclusive algorithm de...

Page 21: ...lation 1 Valves only 2 Fan only 3 Valves and fan 0 P05 Heating output type 0 NC ON OFF valve 1 NA ON OFF valve 0 P06 Cooling output type 0 NC ON OFF valve 1 NA ON OFF valve 0 P07 Fan output type 0 Direct action 1 Reversed action 0 P08 Supply water sensor input 0 Do not show temperature 1 Show temperature 2 Bi metallic contact 3 Window contact 4 Reversed window contact 0 P09 De stratification 0 Neve...

Page 22: ...2 Room temperature correction offset C 5 0 5 0 10 0 P13 Heating set point knob lower limit C 5 0 35 0 30 0 P14 Heating set point knob upper limit C 5 0 35 0 10 0 P15 Cooling set point knob lower limit C 5 0 35 0 30 0 P16 Cooling set point knob upper limit C 5 0 35 0 0 0 P17 Anti freeze threshold temperature C 0 0 15 0 0 0 P18 Economy reduction C 0 0 10 0 0 2 P19 Ambient temperature hysteresis C 0 ...

Reviews: