Minimum average water temperature
If the fan coil runs continuously in cooling
mode in an environment with high
relative humidity, condensate may form
on the air flow outside the appliance.
This condensate could drip onto the
floor and onto any underlying objects.
To prevent condensation phenomena on
the external structure of the appliance
with the fan running, the average water
temperature must not drop below
the limits indicated in the table. These
limits depend on the temperature and
humidity conditions of the room air.
These limits refer to operation with the fan
running at minimum speed.
Condensation may form in the event the
fan is off for a prolonged period and cold
water flows in the coil;
therefore, we
recommend installing the 3-way valve
(accessory).
OPERATING LIMITS
Water temperature
In order to prevent air stratification in
the environment and thus have a better
mixture, the fan coil should not be
supplied with water that is hotter than
65°C.
Using water at a very high temperature
can cause creaking due to the heat
expansion of the elements (plastic and
metal), however, this does not cause
damage to the unit unless the maximum
operating temperature is exceeded.
030
040
130
140
230
240 330
340
Maximum water inlet temperature
°C
80
Maximum water inlet temperature recommended
°C
65
Maximum operating pressure
kPa
800
Minimum water flow rate (Main coil)
l/h
80
80
80
80
80
80
150
150
Maximum water flow rate (Main coil)
l/h
1000
1000
1000
1000
1000
1000
1500
1500
Minimum water flow rate (Heating Only Coil)
l/h
50
-
50
-
50
-
100
-
Maximum water flow rate (Heating Only Coil)
l/h
500
-
500
-
500
-
800
-
Environment temperature limits (Ta)
°C
0° < Ta < 40°
Relative humidity limits in the environment (R.H.)
R.H. < 85%
Electric power supply
230V ( ±10% ) ~ 50Hz
Protection rating
IP
20
MINIMUM AVERAGE WATER TEMPERATURE [°C]
Dry-bulb temperature of room temperature
21
23
25
27
29
31
Wet-bulb temperature
of room temperature
15
3
3
3
3
3
3
17
3
3
3
3
3
3
19
3
3
3
3
3
3
21
6
5
4
3
3
3
23
-
8
7
6
5
5
The earth leakage current of several
devices placed under the same circuit
breaker is summed, therefore we
recommend paying attention to the
calibration value of the circuit breaker and,
if necessary, consider splitting the
installation in more circuits, each of which
protected by its own circuit breaker.
Summary of Contents for VES030
Page 1: ...VES030 VES040 VES130 VES140 VES230 VES240 VES330 VES340 IVES0LJ 1707 5880761_01 ...
Page 2: ...OSSERVAZIONI REMARKS REMARQUES OBSERVACIONES HINWEISE ...
Page 50: ...VES_I030 VES_I040 VES_I130 VES_I140 VES_I230 VES_I240 VES_I330 VES_I340 5880751_01 17 07 ...
Page 51: ...OSSERVAZIONI REMARKS REMARQUES OBSERVACIONES HINWEISE ...
Page 59: ...10 5880751_01 TECHNICAL DATA ...