54
SWP_5287500_00
12.4. MANUFACTURER
(COS)
/ CONFIGURATION
(CFN) BRANCH TABLE OF
PARAMETERS
PARAMETER
DEFAULT
LIMITS
UNIT
DESCRIPTION
H01
60
H02-60
°C
Max. boiler water set point value achievable with
HP
H02
30
30-H01
°C
Min. boiler water set point value
H03
15
H04-30
°C
Max. outside air set point
H04
0
-15
°C
Min. outside air set point
H05
8
H04-H03
°C
Outside air set point for heating element activation
H06 5
H06
5
0-15
°C
Heating element deactivation differential
H07
65
H01-70
°C
Thermal shock set point
H08
365
1-365
days
Anti-bacterial treatment cycle frequency
H09
3
01-05
Num(1)
Number of cycles per individual anti-bacterial
treatment
H10
15
15-30
min
Duration of each cycle (time during which the
thermal shock temperature is maintained)
H11
24
6-24
hrs
Interval between two consecutive cycles
H12
1
0-01
Num(1)
Confi gure the polarity of digital input ID1 [1=active if
the contact is open]
H13
1
0-01
Num(1)
Confi gure the polarity of digital input ID2 [1=active if
the contact is open]
H14
0
0-01
Num(1)
Confi gure the polarity of digital input ID3 [1=active if
the contact is open]
H15
0
0
°C
S1 probe offset (input AI1)
H16
0
0
°C
S2 probe offset (input AI2)
H17
0
0-01
Num(1)
Establish the mains power frequency [0=50 Hz]
H18
0
0-255
Num(3)
Manufacturer password (for accessing level 2
parameters)
H19
0
0-01
Num(1)
Select °C or °F [0=°C]
H20
90
0-255
sec*10
Min. time between switching off and switching on -
OFF-ON time [expressed in tens of sec.]
H21
100
0-255
sec*10
Min. time between two consecutive switch-ons -
ON-ON time [expressed in tens of sec.]
H22
30
0-255
sec.
Time probe S1 remains at the boiler set point value
H23
1
0-1
Num(1)
Enable Autostart function [1=active]
H24
40
35-100
%
Min. speed expressed as a percentage, from 35 to
100%
H25
100
H24-100
%
Max. speed expressed as a percentage, from H24
to 100%
H26
3
0 -15
°C
Heat pump activation differential (Automatic
operation)
H27
60
H02-70
°C
Max. boiler water set point value (Manual
operation)
H28
3
0-15
°C
Heating element activation differential (Manual
operation)
H29
1
0-1
Num(1)
Enable AI2 probe [1=active]
H30
0
0-1
Num(1)
Enable I2 digital input [1=active]
H31
0
0-1
Num(1)
Enable I3 digital input [1=active]
H32
1
0-1
Num(1)
Enable anti-bacterial treatment
H33
1
0-1
Num(1)
Enable dynamic set point
H34
1
0.5-2
Num
Balancing line tilt
H35
20
15-25
°C
Outside air temperature above the value at which
balancing began
H36
10
5-10
°C
Range of the outside air on which the set point
functions
Summary of Contents for SWP200
Page 2: ......
Page 31: ...DOMESTIC WATER HEAT PUMP installation maintenance SWP S W P _ 5 2 8 7 5 0 0 _ 0 0 GB ...
Page 32: ......
Page 61: ...POMPE À CHALEUR EAU SANITAIRE installation maintenance SWP SWP_5287500_00 FR ...
Page 62: ......
Page 91: ...BRAUCHWASSER WÄRMEPUMPE Installation Wartung SWP S W P _ 5 2 8 7 5 0 0 _ 0 0 DE ...
Page 92: ......
Page 122: ......
Page 151: ......
Page 152: ......
Page 153: ......