27
FITTING THE CONNECTION PIPE
Outdoor unit
Indoor unit
GAS line
LIQUID line
Condensate discharge
Siphon
OUTDOOR UNIT BELOW AND INDOOR UNIT
ABOVE
In this case it is necessary to install a siphon
(F) every 10 metres of height difference on
the suction piping (C) in order to block the
outflow of refrigerant and thereby to avoid
liquid returning to the compressor. The
connection pipes must be insulated. The
maximum height difference between the
indoor unit and the outdoor unit must not
exceed the values indicated in the table.
WARNING
Wrap pipe insulating material around the joint
on the indoor unit and secure it with plastic
straps to avoid condensate forming at the joints.
OUTDOOR UNIT ABOVE AND INDOOR UNIT
BELOW
In this case, provision must be made on the
suction piping (C) for siphons (F) every 3
metres of height difference. The purpose of
these siphons is to enable oil to be returned
to the compressor. The connection pipes must
be insulated. The maximum height difference
between the indoor unit and the outdoor unit
must not exceed the values indicated in the
table.