14
OUTDOOR UNIT
GENERAL DATA
(1) Sound pressure measured in semi anechoic chamber at a distance of 1 m from the source.
(1) The rated power input (rated current input) is the maximum input electrical power (maximum current input) from the system, in accordance with the Standards EN-
60335-1 and EN-60335-2-40.
SGE250
SGE350
SGE500
SGE700
Outdoor unit
Type of fan
Type
Axial
Air flow rate
Maximum
m3/h
1750
1800
2100
3500
Sound power
Maximum
dB(A)
62,0
63,0
63,0
67,0
Sound pressure (1 m) (1)
Maximum
dB(A)
55,5
56,0
56,0
59,0
Compressor
Type
type
Inverter rotary
Refrigerant
type
R32
R32
R32
R32
Refrigerant charge
kg
0,55
0,55
1,08
1,42
Potential global heating
GWP
675kgCO2eq
Equivalent CO2
t
0,37
0,37
0,73
0,96
Indoor unit
SGE250W
SGE350W
SGE500W
SGE700W
Outdoor unit
SGE250
SGE350
SGE500
SGE700
Electric data
Rated power input (1)
kW
2,2
2,2
2,5
2,5
Rated current input (1)
A
10,0
10,0
13,0
15,5
Refrigeration pipework
Diameter of liquid refrigerant connections mm (inch)
6,35 (1/4”)
6,35 (1/4”)
6,35 (1/4”)
9,52 (3/8”)
Diameter of refrigerant gas connections
mm (inch)
9,52 (3/8”)
9,52 (3/8”)
12,7 (1/2”)
15,9 (5/8”)
Maximum refrigerant tube length
m
25
25
30
50
Maximum refrigerant line level difference
m
10,0
10,0
20,0
25,0
Refrigerant to be added
g/m
12
12
12
24
Power supply
Power supply
220-240V ~ 50Hz