USER Menu
Note:
Chiller 2° Cooling Set: second cold functioning mode set point that
can be used as an alternative to the first if the function is enabled
Chiller 2° Heating Set: second heat pump functioning mode set
point that can be used as an alternative to the first if the function
is enabled
Note:
Multichiller Enable: enables chiller introduction/disconnection. If
OFF, all chillers are requested always switched-on, independently
from the temperatures detected. Time period controls, global on/off
and switching-off of the individual chillers remain always active. The
Multichiller with this parameter in OFF only functions as plant super-
visor
Global On/Off: centralised switch on/off control of all chillers.
Chiller Cooling Set: cold functioning mode set point that is set for all chil-
lers
Chiller Heating Set: heat pump functioning mode set point that is
set for all chillers
Actual Cooling Set: cold functioning mode set point used currently by
the chillers (can be different to Chiller Cooling Set as the double set
point or multifunction input could be used to determine the work set
point)
Actual Heating Set: heat pump functioning mode set point used
currently by the chillers (can be different to Chiller Heating Set as
the double set point or multifunction input could be used to deter-
mine the work set point)