PCO1 card Inputs/Outputs
ANALOGUE INPUTS
FUNCTION
TYPE OF INPUT
B1
Multifunction input
0 - 20 mA
B2
Multifunction input
0 - 5 Vcc
B3
Multifunction input
NTC 10k Temperature probe
B4
SIW
NTC 10k Temperature probe
B5
SUW
NTC 10k Temperature probe
B6
SUW2
NTC 10k Temperature probe
N.B: SUW3 cannot be managed without PCOE
DIGITAL INPUTS
FUNCTION
ID1
Not used
ID2
Not used
IDI3
Enabling of double set point (2° Set) Contact closed = double set enabled
ID4
Enabling of multifunction inputs (Mult) Contact closed = multifunction enabled
ID5
Flow meter 1 (FL1)
ID6
Flow meter 2 (FL2)
ID7
Flow meter 3 (FL3)
ID8
Not used
DIGITAL OUTPUTS
FUNCTION
ID1
Summary of chiller and Multichiller global alarms
ANALOGUE OUTPUTS
FUNCTION
Not used
PCOE card Inputs/Outputs
ANALOGUE INPUTS
FUNCTION
TIPO INGRESSO
B1
SIW
NTC 10k Temperature probe
B2
SUW
NTC 10k Temperature probe
B3
SUW2
NTC 10k Temperature probe
B4
SUW3
NTC 10k Temperature probe
DIGITAL INPUTS
FUNCTION
Not used
DIGITAL OUTPUTSI
FUNCTION
Not used
ANALOUE OUTPUTS
FUNCTION
Not used