Heat Recovery Units Installation, Use and Maintenance Manual
page 9
1.7 Accessories technical data
HRS_W UNIT WITH WATER POST-HEATING SECTION
The use of the coil is requested when post-heating is necessary and must be fixed directly inside the heat recovery unit.
Values referring to the following conditions: Water 70/60 °C; Air inp. T = 8°C; Nominal air flow rate.
HRS_ED ADJUSTMENT DAMPER
The adjustment damper is made up from a galvanised sheet steel frame with adjustable louvered fins.
Model
B (mm)
A (mm)
HRS090ED
260
210
HRS160ED
290
310
HRS190ED
330
310
HRS230-ED
410
410
BATTERIA POST-RISCALDAMENTO
WATER HEATING COIL - BCR
090
160
190
230
300
390
Resa termica /
Heating capacity
kW
8.2
12.2
14.4
20.3
24.2
29.9
Geometria /
Geometry
25x22
25x22
25x22
25x22
25x22
25x22
Tubi per rango /
Pipes per row
n°
14
18
18
22
22
22
Ranghi /
Rows
n°
2
2
2
2
2
2
Passo alette /
Fins spacing
mm
2.5
2.5
2.5
2.5
2.5
2.5
Temp. uscita aria /
Outlet air temperature
°C
33.4
30.8
30.2
33.2
31.3
29.7
Perdita di carico lato aria /
Air pressure drop
Pa
25
32
35
24
36
38
Perdita di carico lato acqua /
Water pressure drop
kPa
8
14
15
17
22
30
Diametro collettori /
Connection diameter
Ø gas
3/4
3/4
3/4
3/4
3/4
3/4
Peso /
Weight
kg
2.5
2.5
2.5
5
5
6.5
HRS_CS SECTION WITH WATER COIL
The HRS_CS module contains a water coil and must be positioned outside the machine in front of the introduction vent.
The condensate drip tray in stainless steel with low condensate drain connection.
Model
090
160
190
230
390
A (mm)
500
600
700
700
700
B (mm)
410
500
500
600
600
C (mm)
450
450
480
660
710
D (mm)
260
290
310
410
410
E (mm)
210
310
330
410
410
Ø1 (gas)
3/4"
3/4"
3/4"
3/4"
1"
Ø2 (mm)
22
22
22
22
22
Summary of Contents for HRS 030
Page 1: ...HEAT RECOVERY UNIT Installation Use and Maintenance Manual HRS HRS W 4530600_00 dated 0904 ...
Page 26: ...Heat Recovery Units Installation Use and Maintenance Manual page 29 ...
Page 27: ...Heat Recovery Units Installation Use and Maintenance Manual page 30 ...
Page 28: ...Heat Recovery Units Installation Use and Maintenance Manual page 31 ...
Page 29: ......