AERMEC FK260 Use And Installation  Manual Download Page 10

10

Aermec. 16.01. 5140901_01

INSTALLATION

7. 

INSTALLATION

7.1. 

PRECAUTIONS FOR INSTALLATION OF 
THE UNIT

To guarantee the unit operates correctly, the 

choice of location for the installation must 

meet the following criteria:

• 

The external parts of the unit must be 

installed so as to avoid the recirculation 

of air discharged from the unit and that 

there is sufficient space around the 

machine for maintenance operations.

• 

The place of installation should have 

good ventilation so the external parts 

of the unit can suck in and blow out a 

sufficient amount of air. Make sure there 

are not obstacles near the air intake and 

delivery sockets. 

• 

Remove any obstacles which may be 

blocking the intake or discharge of air.

• 

The position of installation should be 

solid enough to support the weight of the 

unit, and it must be possible to absorb 

vibrations and insulate noise. Ensure that 

the air and noise coming from the unit do 

not disturb your neighbours.

• 

The installation position must ensure 

that the external parts are not covered 

by snow and it not subject to the effects 

produced by fumes from fuel and oils.

• 

Avoid direct exposure of the unit to solar 

radiation: it is recommended to install 

protection.

• 

The place of installation should guarantee 

the drainage of rainwater.

• 

Always ensure adequate condensate 

drainage is installed. 

The condensation 

discharge pipe is NOT supplied with 

the unit.

 It should only be installed under 

the base of the unit and connected to a 

pipe of a sufficient diameter.

• 

The site of installation must be positioned 

so that the discharge air outlet is not 

exposed to strong winds and the air 

discharged must be free to disperse into 

the atmosphere.

• 

There should be no obstacles near the air 

delivery and intake sockets in the internal 

part so that air can circulate freely.

• 

Ensure the installation complies with the 

minimum technical clearances specified 

in the installation diagram. 

• 

The installed unit must be horizontal and 

level.

• 

Installation in dusty or smoky 

environments (kitchens with cookers, 

etc.) can clog the filter, the exchanger and 

the condensate discharge pipe, resulting 

in reduced performance and the risk of 

condensate water overflow. 

• 

If the unit is installed in a kitchen, ensure 

that the fume extractor hood is sufficient 

to extract all fumes from the cookers. 

Install the unit far away from cookers 

to avoid the intake of fumes into the air 

conditioner.

• 

Install the unit further than 1m away from 

other electrical appliances such as TVs, 

radios, audio equipment, etc.

• 

Do not install the unit in a location where 

it could be affected by inflammable gas 

leaks.

• 

Do not install the unit near a laundry, 

bathroom, shower or swimming pool.

• 

To avoid problems with the air 

conditioner, avoid installation in locations:

• 

Where there is a lot of oil.

• 

Where there is an acid base.

• 

Where the power supply is irregular.

7.2. 

POSITIONING

Wall

frame

Wooden 

Sunshade 

board

Rubber 

plate

6~10mm

Support

Horizontal line

Sun shield

Wall

Frame 

made of 

wood
Plate 

made of 

rubber

Horizontal line

Supporter

Carry out the following installation procedure:

• 

Remove the sticker from the front panel.

• 

Put the unit in the installation hole.

• 

During installation the unit should be 

inclined by 6 to 10 mm towards the 

rear as shown in the figure, to avoid the 

amplification of noise or vibrations.

• 

The installation hole must be robust 

enough to avoid expanding over time 

and to avoid causing noises or vibrations.

• 

Fill the space between the hole and the 

unit with polyurethane foam or similar for 

proper fixing and insulation.

• 

Use a suitably sized bracket that can 

support the weight of the unit.

• 

Level the bracket.

Summary of Contents for FK260

Page 1: ...EN USE AND INSTALLATION MANUAL Aermec 16 01 5140901_01 FK260 FK360 Energy efficiency A 5140901_01...

Page 2: ...NS FOR INSTALLATION OF THE UNIT 10 7 2 POSITIONING 10 7 3 MINIMUM TECHNICAL CLEARANCES 11 7 4 CONDENSATE DRAINAGE 11 7 5 ELECTRICAL WARNINGS 12 7 6 UNIT DIMENSIONS 12 8 WIRING DIAGRAMS 13 9 OPERATING...

Page 3: ...laws All specifications are subject to change without prior notice Although every effort has been made to ensure precision Aermec does not assume any responsibility for any errors or omissions Dear c...

Page 4: ...Y ONLY BE FOLLOWED BY SPECIALISED TECHNICIANS OR QUALIFIED PERSONNEL Make sure that other types of coolant do not contaminate the R32 The gas tank must be kept in a vertical position during filling Ap...

Page 5: ...s Service these operations must only be carried out by Personnel with the specific technical skills Ensure that the power supply and the installed output are adequately scaled to supply the air condit...

Page 6: ...cally check that the installation conditions of the unit have not been altered and have the system checked by a qualified engineer Do not remove the protection grilles Do not insert your hands or any...

Page 7: ...remote control Control panel on the machine Compact unit with reduced dimensions Three possible functions Cooling Dehumidification Ventilation only Class A energy efficiency Contained sound emissions...

Page 8: ...enser attachment diameter mm 7 7 Fan Type Axial Axial Air flow rate m3 h 800 1200 Sound pressure maximum dB A 56 58 Sound pressure medium dB A 54 56 Sound pressure minimum dB A 52 54 Sound power maxim...

Page 9: ...9 Aermec 16 01 5140901_01 6 DESCRIPTION OF COMPONENTS Inner side Air filter Outer side...

Page 10: ...the air delivery and intake sockets in the internal part so that air can circulate freely Ensure the installation complies with the minimum technical clearances specified in the installation diagram...

Page 11: ...re starting up the unit Slide the frame of the unit from the base Install the drainage tub on the corner and fix it with two screws as shown in the figure Connect the drainage pipe NOT provided to the...

Page 12: ...Ensure that the earthing cable is connected to the building s earthing connection system Ensure that a differential switch suitable for leaks to the ground is installed Do not connect the earth cable...

Page 13: ...tilator PE W V U N AC L AP1 BN M BU YEGN BU YE RD Kompressor CN1 W V U YEGN 2 XT 1 berstrom ausl ser RD RD WARNUNG 15K 50K 20K CN3 RT1 RT2 RT3 WH BK Temp F hler Lufteintritt Temp F hler Register Temp...

Page 14: ...e or generate noise Has a check for refrigerant leaks been performed Poor performance Is the thermal insulation sufficient It could cause condensate and dripping water Does the unit correctly drain th...

Page 15: ...hese steps the filter is still dirty fill a tub with lukewarm water and some non aggressive cleanser and soak it for a few minutes Next dry it with a cloth 5 Otherwise have a specialised technician cl...

Page 16: ...to select the fan speed 5 SWING button Press this button to select the fan mode from left to right 6 TIMER button Timer function for setting the time the unit is switched on or off Temp function to se...

Page 17: ...d FAN Ventilation only mode the unit operates in ventilation mode In this case press the FAN button repeatedly to adjust the ventilation speed 3 button Function 1 Pressing or once will increase or red...

Page 18: ...GRAMMED START UP FUNCTION When the unit is turned off pressed the Timer button to set the programmed start up function The T ON and H icons on the display will start to blink In 5 seconds press the bu...

Page 19: ...careful not to invert the polarity Close the battery cover NOTE When batteries are replaced use new batteries of the recommended type Remove the batteries if the remote control is not used for extende...

Page 20: ...room temperature We recommend that you do not keep the air jets direct instead set the unit to Swing mode Make sure the doors and windows are closed well Avoid opening the doors and windows of the roo...

Page 21: ...ssor protection from overloading Contact specialised personnel or the Aermec Assistance Service L9 Power supply protection Contact specialised personnel or the Aermec Assistance Service H5 Module temp...

Page 22: ...suggested by the producer of the material The unit must be installed in a space that respects the minimum allowed dimensions Please carefully observe the following table Verify that the maintenance ar...