1508 - 5138800_00

5 SLAVE fa coil units for each zone).

4) Control of a fan coil unit system, plus man-

agement of the heat pump (if compatible 
with the VMF system).

5) Control of a fan coil unit system, heat pump 

and management of the domestic hot water 
system (VMF-ACS).

6) Control of a fan coil unit system, heat pump, 

domestic hot water production and addition-
al circulators (up to a maximum of 12 using 
three additional VMF-CRP modules).

7) Control of a fan coil unit system, heat pump, 

domestic hot water production, additional 
circulators and management of heat recovery 
units, maximum 3, (with the ability to handle 
up to 3 VMF-VOC sensors) or a boiler.

• The VMF system can operate and manage, 

through a VMF-E5N / VMF-E5B panel, a maxi-
mum of 64 zones consisting of a MASTER fan 
coil unit and a maximum of 5 SLAVE fan coil 
units connected to each MASTER, for a total 
of 384 fan coil units. 

• Besides the central control supplied by the 

VMF-E5N / VMF-E5B panel, the MASTER fan 
coil units must be provided with a local con-
trol interface; this interface can be mounted 

on the fan coil unit (only for the models 
(where it is possible) or be mounted into a 
wall panel (VMF-E4 / VMF-E4D).

• Different functions can be controlled through 

the VMF-E5N / VMF-E5B panel, including:

-  Identify the different zones giving a name for 

each one.

- Check and set the ON-OFF function and the 

set point temperature of each zone.

-  Set and manage the set point temperature of 

the heat pump.

-  Scheduling time clocks.
• Simple installation of the fan coil unit system 

through the SELF-MONITORING function of 
the MASTER fan coil units.

• 

sĞƌƐŝŽŶƐǁŝƚŚŵŝĐƌŽƉƌŽĐĞƐƐŽƌĐŽŶƚƌŽůůĞƌ͗

With or without water valve.
Versions with microprocessor controller have a 

display on the front panel showing the main 
functions of the unit.

The versions with microprocessor controller 

need to be combined with one of the two 
available control systems (accessories PFW2 
or TLW2) provided as required as a neces-
sary accessory for the unit operation allowing 

turning on, turning off and all the fan coil  
unit control and programming operations.

dŚĞ ƚǁŽ ĐŽŶƚƌŽů ƐLJƐƚĞŵƐ ĐĂŶ ďĞ ƵƐĞĚ Ăƚ ƚŚĞ

same time on the same fan coil unit.

The control system checks all the functioning 

parameters and carries out all the operations 
necessary to enable the required room condi-
tions to be maintained.

The control system also provides some auto-

matic functions to increase comfort and 
make the most frequently repeated opera-
tions easier:

- Minimum temperature sensor; in order to 

avoid cold air blasts in the winter mode, 
allowing ventilation only if the water in the 
system is hot. 

-  Auto Restart mode, after a power outage the 

FCW unit starts again automatically with the 
same settings that it had at the time of stop-
ping (with the exception of the Timer and 
Sleep settings).

/DWKZdEd/E&KZDd/KE

tZE/E'͗dŚĞĨĂŶĐŽŝůƵŶŝƚŝƐĐŽŶŶĞĐƚĞĚƚŽƚŚĞƉŽǁĞƌƐƵƉƉůLJ
ĂŶĚĂǁĂƚĞƌĐŝƌĐƵŝƚ͘KƉĞƌĂƚŝŽŶƐƉĞƌĨŽƌŵĞĚďLJƉĞƌƐŽŶƐǁŝƚŚŽƵƚ
ƚŚĞƌĞƋƵŝƌĞĚƚĞĐŚŶŝĐĂůƐŬŝůůƐĐĂŶůĞĂĚƚŽƉĞƌƐŽŶĂůŝŶũƵƌLJƚŽƚŚĞ
ŽƉĞƌĂƚŽƌŽƌĚĂŵĂŐĞƚŽƚŚĞƵŶŝƚĂŶĚƐƵƌƌŽƵŶĚŝŶŐŽďũĞĐƚƐ͘
dŚĞƵŶŝƚƐŚĂůůďĞŝŶƐƚĂůůĞĚŝŶĂĐĐŽƌĚĂŶĐĞǁŝƚŚEĂƚŝŽŶĂůtŝƌŝŶŐ

Regulations.”

D>&hEd/KE
/Ŷ ƚŚĞ ĐĂƐĞ ŽĨ Ă ŵĂůĨƵŶĐƚŝŽŶ ƌĞŵŽǀĞ ƉŽǁĞƌ ƚŽ ƚŚĞ ƵŶŝƚ ƚŚĞŶ
ƌĞĂƉƉůLJŝƚĂŶĚƐƚĂƌƚƚŚĞƵŶŝƚĂŐĂŝŶ͘/ĨƚŚĞƉƌŽďůĞŵŽĐĐƵƌƐĂŐĂŝŶ͕
ĐĂůůLJŽƵƌĂƌĞĂĨƚĞƌͲ^ĂůĞƐƐĞƌǀŝĐĞĚĞƉĂƌƚŵĞŶƚƉƌŽŵƉƚůLJ͘

WKtZ d, &E K/> hE/d KE>z t/d, ϮϯϬ sK>d͕ ^/E'>

PHASE, 50 Hz

Use of other power supplies could cause permanent damage to 
the fan coil unit.

h^ d, Έd>tϮΉ ZDKd KEdZK> KZ d, t/Z KEͳ
dZK>WE>ΈW&tϮΉdKdhZEd,&EK/>hE/dKEE

OFF 

Do not turn the fan coil unit on or off using the auxiliary switch 
except in an emergency.

KEKdWh>>d,>dZ/>>

It is very dangerous to pull, tread on or crush the electrical 
power cable or fix it with nails or drawing pins.
A damaged power cable can cause short circuits and personal 
injury.

KEKdWhdEzd,/E'/Ed,/ZKhd>d^

Do not put anything at all in the air outlet slots.
This could cause injury to people and damage to the fan.

KEKdh^d,&EK/>hE/d/DWZKWZ>z

Do not use the fan coil unit in animal husbandry applications.

sEd/>d/E'd,ZKKD

Periodically air the room in which the fan coil unit has been 
installed; this is particularly important if the room is occupied 
by many people, or if gas appliances or sources of odours are 

present.

KZZd>zKEdZK>>/E'd,dDWZdhZ

The room temperature should be controlled in order to provide 
maximum comfort to the people in the room, especially if they 
are elderly, children or ill, avoiding sudden changes in tempera-
ture between the outside and inside above 7 °C in summer. 
Careful choice of the room temperature will lead to energy sav-
ings.

KZZd>z:h^d/E'd,/Z:d

The air coming out of the fan coil unit must not strike people 
directly; in fact, even if at a temperature that is higher than the 
room temperature, it could cause a cold sensation and resulting 
discomfort. 
Only adjust the vertical blades by hand.
In the versions with microprocessor controller adjust the hori-
zontal blade with the LOUVRE or SWING key of the remote con-
trol or the wired control panel. 
In the versions without microprocessor controller adjust the 
horizontal blades by hand.

hZ/E'KWZd/KE

Always leave the filter in the fan coil unit during operation oth-
erwise dust in the air will dirty the surfaces of the coil.

t,d/^EKZD>

During cooling, water vapour may be present in the air dis-
charge.
During heating it might be possible to hear a slight hiss around 
the fan coil unit. Sometimes the fan coil unit might give off 
unpleasant smells due to the accumulation of substances from 
the air of the room (especially if the room is not ventilated regu-
larly. Clean the filter more often).

During operation, there could be noises and creaks inside the 
device, due to the thermal expansion of the various compo-
nents (plastic and metallic), but this does not indicate a mal-
function and does not cause damage to the unit unless the 
maximum input water temperature is exceeded.

Summary of Contents for FCW Series

Page 1: ...42VLN IFCW3LJ 1508 5138800_00 IT GB FR DE ES pag 5 pag 26 pag 47 pag 68 pag 89 VENTILCONVETTORE PER INSTALLAZIONE A PARETE t DKhEd E K hE d s Ed K KEs d hZ WKhZ E d d KE DhZ GEBL SEKONVEKTOR F R WAND...

Page 2: ...egislaci n de armonizaci n pertinente de la Uni n CEIEN60335 2 40 2005 CEIEN60335 2 40 A1 2007 CEIEN55014 1 2008 CEIEN55014 2 1998 CEIEN61000 6 1 2007 CEIEN61000 6 3 2007 Soddisfacendo cos i requisiti...

Page 3: ...3 General information 34 Important information Operational limits 35 Direction of the air flow 36 Control keys and signals FCW with microprocessor controller 37 TLW2 Infra red remote control 38 PFW2 W...

Page 4: ...aged in transit If any anomalies are found immediately notify the haulier of the damage immediately notify the vendor of the damage t d The electric and electronic equipment must be handled separately...

Page 5: ...perations that involve dismantling of the fan coil unit or its components to ensure the maximum fan coil unit efficiency is restored Operations Internal cleaning annually or after long periods of inac...

Page 6: ...tions Several versions of FCW fan coil units are available in order to satisfy all types of installations with internal 2 way valve with internal 3 way valve without valve Each version is available Wi...

Page 7: ...all the operating parameters of the unit These parameters are shown on a liquid crystal dis play making programming operations easier The remote control is supplied with a bracket allowing it to be hu...

Page 8: ...ts again automatically with the same settings that it had at the time of stop ping with the exception of the Timer and Sleep settings DWKZd Ed E KZD d KE t ZE E d K d E t Regulations D hE d KE WKt Z d...

Page 9: ...0 V and ensure it remains within the limit of 10 with respect to the nominal value OPERATING ENVIRONMENT d of urban non marine atmosphere with non corrosive and non dusty h which the unit must operate...

Page 10: ...nually h d E d s Zd turn the vertical blades as indicated in the diagram both in heating or cooling mode it is advisable for the air flow not to hit people directly DKdKZ KZ KEd E cause a malfunction...

Page 11: ...5 C automatic ventila tion swinging blades Second press Heating with set point 22 C automatic venti lation swinging blades Third press Fan coil unit turned off t hy Set the operation mode Cooling Firs...

Page 12: ...f the horizontal blades Khs Z Press this button to regulate the vertical air flow with 4 fixed positions plus swinging blades E Press this button to transmit the parameters shown on the display to the...

Page 13: ...attery cover DWKZd Ed The two control types wired control panel and remote control can be used at the same time on the same fan coil unit The batteries have an average life of 10 months when used norm...

Page 14: ...off but powered it sets and displays the hours off before the programmed turn on t E KZ KEd Press this button to control the vertical air flow The first press starts the blades swinging The second pre...

Page 15: ...rameters shown on the LCD to the main control unit t d WW E t E d hdKD d WZK Z DD d With AUTO programme the control system decides the type of operation COOL or HEAT on the basis of the water and room...

Page 16: ...shown on the LCD to the main control unit 6 PFW2 TLW2 WZ d KE K OR z The fan coil comes on and the display is switched on WZ d DK z Press the MODE key repeatedly until the word FUN appears on the dis...

Page 17: ...If you wish to stop the blade in a particular position press the SWINGkey again WZ d E z d t To transmit the new parameters shown on the LCD to the main control unit d PFW2 TLW2 Tset 3 C Tset 2 C Tse...

Page 18: ...e control dK E d d D Z dd E TLW2 Press the key to cancel the timer setting PFW2 Press the TIMER key for 3 seconds to cancel the timer setting Press the or key to manually turn ON the unit while the ti...

Page 19: ...wn in the manual determined by the room temperature and humidity conditions These limits refer to unit operation with fan at minimum speed In order to avoid air stratification and therefore achieve be...

Page 20: ...on densate is connected to the sewage sys tem The service hole for the piping can be located on the right or left of the unit The support wall must be sturdy and not subject to vibrations Do not insta...

Page 21: ...Screws Screw covers nents of the unit paying attention that the debris from the materials used for the installation do not block the fan or obstruct the filters or the grilles After installation perfo...

Page 22: ...cable FCW_2V FCW_3V FCW_VL FCW_2VN FCW_3VN FCW_VLN IG 2A 1 5mm2 WARNING operations on the unit d ent circuit W s To protect the unit against short circuits s The electrical power cable must be of the...

Page 23: ...s or a rectangular electri cal box The panel cable is 4 metres long and is fitted with connector B for con nection to the fan coil circuit board as shown in the wiring diagrams To install the wired co...

Reviews: