21
English
Minimum average water temperature
If the fan coil is working in continuous
cooling mode in an environment where
the relative humidity is high, condensate
might form on the air delivery and
on the outside of the device. This
condensate might be deposited on any
objects underneath and on the floor.
To avoid condensate on the external struc-
ture of the apparatus with the fan in
operation, the average temperature of
the water must not be lower than the lim-
its shown in the table below, that depend
on the thermo-hygrometric condition of
the air in the environment.
The limits mentioned above refer to opera-
tion while the fan is set
to its minimum speed level.
TECHNICAL DATA AND OPERATING LIMITS
Performance values refer to the following conditions:
- at the maximum motor speed;
- the total input power is determined by adding the input power
for the unit to the input power for the accessories connected and
declared in the corresponding manuals.
Water temperature
In order to prevent air stratification in the
room, and therefore to achieve improved
mixing, it is advisable not to supply the fan coil
with water at a temperature over 65°C.
The use of water at high temperatures
could cause squeaking due to the different
thermal expansions of the elements (plastics
and metals), this does not however cause
damage to the unit if the maximum operating
temperature is not exceeded.
MACHINE PURPOSE
The fan coil is a room air treatment terminal unit for both winter and summer operation.
FCLI VERSION
Cassette-type fan coil with Inverter for installation in suspended ceilings; can be integrated in standard 600x600 and
840x840 panelling.
DESCRIPTION OF THE UNIT
AVAILABLE SIZES
The cassette-type fan coils of the FCLI range are available in:
for 2-pipe systems
FCLI 32 (600x600)
FCLI 42 (600x600)
FCLI 62 (600x600)
FCLI 82 (840x840)
FCLI 122 (840x840)
For 4-pipe systems
FCLI 34 (600x600)
FCLI 44 (600x600)
FCLI 64 (600x600)
FCLI 124 (840x840)
GLLI100/GLFI10/GLLI100N/GLFI10N/GLFI10M/GLLI100EH/GLFI10EH
-
GLLI 20 (840x840): Grille unit with suction and delivery filter, with
manually adjustable fins; requires an external control panel with thermostat and ventilation speed control, with 0-10V output.
GRILLE UNIT (OBLIGATORY ACCESSORY)
FCLI
32
34
42
44
62
64
82
122
124
Maximum recommended temperature
65°C
Maximum water inlet temperature
80°C
Maximum operating pressure
kPa 800 (8 bar)
Minimum operating pressure
kPa 100 (1 bar)
Room temperature limit R.T.
0°C
<Ta<40
°C
Room temperature limit R.H.
R.H.
< 85%
Minimum delivery (heating)
°C
100
50
100
50
150
50
250
350
50
Maximum delivery (heating)
°C
750
400
750
400
1050
400
1750
2450
400
Minimum delivery (cooling)
°C
100
100
100
100
150
150
250
350
250
Maximum delivery (cooling)
°C
750
750
750
750
1050
1050
1750
2450
1750
Maximum input current
A
0.22
0.22
0.33
0.33
0.37
0.37
0.7
0.75
0.75
Power supply
V / Hz
230V (±10%) 50 Hz
230V (±10%) 50/60 Hz
MINIMUM AVERAGE WATER TEMPERATURE [°C]
Ambient air temperature with dry bulb
21
23
25
27
29
31
Ambient air temperature
with wet bulb
15
3
3
3
3
3
3
17
3
3
3
3
3
3
19
3
3
3
3
3
3
21
6
5
4
3
3
3
23
-
8
7
6
5
5
Summary of Contents for FCLI 122
Page 4: ...4 ...
Page 13: ...13 Italiano INSTALLATION MODULE 600 GLLI10 GLFI10 ...
Page 25: ...25 English INSTALLAZIONE MODULO 600 GLLI10 GLFI10 ...
Page 37: ...37 Français INSTALLATION MODULE 600 GLLI10 GLFI10 ...
Page 49: ...49 Deutsch INSTALLATION MODUL 600 GLLI100 GLFI10 ...
Page 61: ...61 Español INSTALACIÓN MÓDULO 600 GLLI100 GLFI10 ...