KEY:
pf: cooling capacity
pa: input power
Processed
water tempe-
rature °C
Outside air temperature (°C)
20
25
30
35
40
45
46
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
4
12.49
3.30
12.16
3.66
11.83
4.02
11.51
4.38
10.93
4.59
9.67
5.13
9.42
5.24
5
12.58
3.30
12.16
3.66
11.95
4.02
11.64
4.38
11.09
4.60
9.84
5.14
9.59
5.25
6
12.68
3.30
12.27
3.67
12.07
4.03
11.77
4.39
11.25
4.61
10.03
5.14
9.77
5.25
7
12.77
3.30
12.38
3.67
12.19
4.03
11.90
4.40
11.41
4.62
10.20
5.15
9.95
5.26
8
12.87
3.30
12.48
3.67
12.31
4.04
12.03
4.41
11.57
4.62
10.40
5.16
10.16
5.27
9
12.97
3.30
12.59
3.67
12.43
4.04
12.16
4.42
11.73
4.63
10.59
5.17
10.36
5.28
10
13.06
3.30
12.70
3.68
12.55
4.05
12.29
4.42
11.89
4.64
10.67
5.18
-
-
11
13.16
3.30
12.80
3.68
12.67
4.06
12.42
4.43
12.06
4.65
-
-
-
-
12
13.25
3.30
12.91
3.68
12.79
4.06
12.55
4.44
12.22
4.65
-
-
-
-
13
13.35
3.30
13.02
3.68
12.91
4.07
12.69
4.45
12.38
4.66
-
-
-
-
14
13.44
3.30
13.13
3.69
13.02
4.07
12.82
4.46
12.54
4.67
-
-
-
-
15
13.54
3.30
13.23
3.69
13.14
4.08
12.95
4.46
12.70
4.68
-
-
-
-
16
13.63
3.30
13.34
3.69
13.26
4.08
13.08
4.47
12.86
4.69
-
-
-
-
17
13.73
3.30
13.45
3.70
13.38
4.09
13.21
4.48
13.02
4.69
-
-
-
-
18
13.82
3.30
13.55
3.70
13.49
4.09
13.33
4.48
13.17
4.70
-
-
-
-
8.19 Cooling capacity and input power
KEY:
pf: cooling capacity
pa: input power
Processed
water tempe-
rature °C
Outside air temperature (°C)
20
25
30
35
40
45
46
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
4
15.11
3.98
14.72
4.41
14.32
4.84
13.92
5.27
13.23
5.53
11.71
6.18
11.40
6.31
5
15.23
3.98
14.72
4.41
14.46
4.85
14.08
5.28
13.42
5.54
11.91
6.19
11.60
6.32
6
15.34
3.98
14.85
4.42
14.61
4.85
14.24
5.29
13.62
5.55
12.14
6.20
11.83
6.33
7
15.46
3.98
14.98
4.42
14.75
4.86
14.40
5.30
13.81
5.56
12.34
6.21
12.04
6.34
8
15.57
3.98
15.11
4.42
14.90
4.87
14.56
5.31
14.00
5.57
12.59
6.22
12.29
6.35
9
15.69
3.98
15.24
4.43
15.04
4.87
14.72
5.32
14.20
5.58
12.82
6.23
12.54
6.36
10
15.80
3.98
15.36
4.43
15.18
4.88
14.88
5.33
14.39
5.59
12.92
6.24
-
-
11
15.92
3.98
15.49
4.43
15.33
4.89
15.03
5.34
14.59
5.60
-
-
-
-
12
16.03
3.98
15.62
4.44
15.47
4.89
15.19
5.35
14.78
5.61
-
-
-
-
13
16.15
3.98
15.75
4.44
15.62
4.90
15.35
5.36
14.98
5.62
-
-
-
-
14
16.26
3.98
15.88
4.44
15.76
4.90
15.51
5.37
15.17
5.63
-
-
-
-
15
16.38
3.98
16.01
4.44
15.90
4.91
15.67
5.38
15.37
5.64
-
-
-
-
16
16.50
3.98
16.14
4.45
16.05
4.92
15.83
5.39
15.56
5.65
-
-
-
-
17
16.61
3.98
16.27
4.45
16.19
4.92
15.98
5.40
15.75
5.65
-
-
-
-
18
16.72
3.98
16.40
4.45
16.33
4.93
16.13
5.40
15.93
5.66
-
-
-
-
8.20 Cooling capacity and input power
CORRECTION FACTORS FOR
∆
T DIFFERENT FROM THE CHILLER RATED VALUE
3
5
8
10
Cooling capacity correction factors
0.99
1
1.02
1.03
Input power correction factors
0.99
1
1.01
1.02
FOULING FACTORS
[K*m2]/[W]
0.00005
0.0001
0.0002
Cooling capacity correction factors
1
098
094
Input power correction factors
1
0.98
0.95
ANR502 HM (400V - 50 Hz)
ANR802 HM (400V - 50 Hz)