![AERMEC ANR R407C Technical Manual Download Page 26](http://html1.mh-extra.com/html/aermec/anr-r407c/anr-r407c_technical-manual_2861792026.webp)
26
KEY:
pf: cooling capacity
pa: input power
Processed
water tempe-
rature °C
Outside air temperature (°C)
20
25
30
35
40
45
46
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
4
12.49
3.45
12.16
3.83
11.83
4.20
11.51
4.58
10.93
4.80
9.67
5.36
9.42
5.48
5
12.58
3.45
12.16
3.83
11.95
4.21
11.64
4.58
11.09
4.81
9.84
5.37
9.59
5.48
6
12.68
3.45
12.27
3.83
12.07
4.21
11.77
4.59
11.25
4.82
10.03
5.38
9.77
5.49
7
12.77
3.45
12.38
3.84
12.19
4.22
11.90
4.60
11.41
4.83
10.20
5.39
9.95
5.50
8
12.87
3.45
12.48
3.84
12.31
4.22
12.03
4.61
11.57
4.83
10.40
5.40
10.16
5.51
9
12.97
3.45
12.59
3.84
12.43
4.23
12.16
4.62
11.73
4.84
10.59
5.41
10.36
5.52
10
13.06
3.45
12.70
3.84
12.55
4.23
12.29
4.62
11.89
4.85
10.67
5.41
-
-
11
13.16
3.45
12.80
3.85
12.67
4.24
12.42
4.63
12.06
4.86
-
-
-
-
12
13.25
3.45
12.91
3.85
12.79
4.25
12.55
4.64
12.22
4.87
-
-
-
-
13
13.35
3.45
13.02
3.85
12.91
4.25
12.69
4.65
12.38
4.87
-
-
-
-
14
13.44
3.45
13.13
3.85
13.02
4.26
12.82
4.66
12.54
4.88
-
-
-
-
15
13.54
3.45
13.23
3.86
13.14
4.26
12.95
4.67
12.70
4.89
-
-
-
-
16
13.63
3.45
13.34
3.86
13.26
4.27
13.08
4.67
12.86
4.90
-
-
-
-
17
13.73
3.45
13.45
3.86
13.38
4.27
13.21
4.68
13.02
4.91
-
-
-
-
18
13.82
3.45
13.55
3.87
13.49
4.28
13.33
4.69
13.17
4.91
-
-
-
-
COOLING MODE
KEY:
pf: cooling capacity
pa: input power
Processed
water tempe-
rature °C
Outside air temperature (°C)
20
25
30
35
40
45
46
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
Pf
Pa
4
15.01
4.20
14.61
4.66
14.22
5.11
13.83
5.57
13.14
5.84
11.63
6.53
11.33
6.67
5
15.12
4.20
14.61
4.66
14.36
5.12
13.99
5.58
13.33
5.85
11.83
6.54
11.52
6.68
6
15.24
4.20
14.74
4.67
14.51
5.13
14.14
5.59
13.52
5.86
12.05
6.55
11.74
6.69
7
15.35
4.20
14.87
4.67
14.65
5.13
14.30
5.60
13.71
5.87
12.26
6.56
11.96
6.70
8
15.47
4.20
15.00
4.67
14.79
5.14
14.46
5.61
13.91
5.88
12.50
6.57
12.21
6.71
9
15.58
4.20
15.13
4.68
14.94
5.15
14.61
5.62
14.10
5.89
12.73
6.58
12.46
6.72
10
15.69
4.20
15.26
4.68
15.08
5.15
14.77
5.63
14.29
5.90
12.83
6.59
-
-
11
15.81
4.20
15.39
4.68
15.22
5.16
14.93
5.64
14.49
5.91
-
-
-
-
12
15.92
4.20
15.52
4.69
15.37
5.17
15.09
5.65
14.68
5.92
-
-
-
-
13
16.04
4.20
15.64
4.69
15.51
5.17
15.24
5.66
14.87
5.93
-
-
-
-
14
16.15
4.20
15.77
4.69
15.65
5.18
15.40
5.67
15.07
5.94
-
-
-
-
15
16.27
4.20
15.90
4.70
15.79
5.19
15.56
5.68
15.26
5.95
-
-
-
-
16
16.38
4.20
16.03
4.70
15.94
5.20
15.72
5.69
15.45
5.96
-
-
-
-
17
16.50
4.20
16.16
4.70
16.08
5.20
15.87
5.70
15.64
5.97
-
-
-
-
18
16.61
4.21
16.29
4.71
16.21
5.21
16.02
5.70
15.82
5.98
-
-
-
-
8.14 Cooling capacity and input power
CORRECTION FACTORS FOR
∆
T DIFFERENT FROM THE CHILLER RATED VALUE
3
5
8
10
Cooling capacity correction factors
0.99
1
1.02
1.03
Input power correction factors
0.99
1
1.01
1.02
FOULING FACTORS
[K*m2]/[W]
0.00005
0.0001
0.0002
Cooling capacity correction factors
1
098
094
Input power correction factors
1
0.98
0.95
8.13 Cooling capacity and input power
ANR502 HM (230V - 50 Hz)
ANR 802HM (230V - 50 Hz)