23.05 – 6755517_09
33
ELECTRIC DATA
The designer must calculate the appropriate line switch, power supply line, connection to the earth wire and connection cables for the section and length of the cables,
depending on:
— The length;
— The type of cable;
— The absorption of the unit and the physical location, and the ambient temperature.
Power supply 220V
Size
100
150
POWER SUPPLY: 6
Cooling performance 12 °C / 7 °C
Cooling total input current
°
A
31.4
36.7
A,P
A
34.3
42.5
Heating performance 40 °C / 45 °C
Heating total input current
°
A
31.6
37.1
A,P
A
34.5
42.9
Electric data
Peak current (LRA)
°
A
170.0
195.0
A,P
A
173.0
200.0
Minimum circuit amperage (MCA)
°
A
50.0
60.0
A,P
A
60.0
70.0
Maximum overcurrent permitted by the protec-
tion device (MOP)
°
A
60.0
80.0
A,P
A
70.0
80.0
(1) Data EN 14511:2018; System side water heat exchanger 53.6 °F / 44.6 °F; External air 95.0 °F
(2) Data EN 14511:2018; System side water heat exchanger 104.0 °F / 113.0 °F; External air 45 °F b.s. / 43 °F b.u
Power supply 460V
Size
100
150
POWER SUPPLY: 7
Cooling performance 12 °C / 7 °C
Cooling total input current
°
A
17.1
19.6
A,P
A
18.7
22.8
Heating performance 40 °C / 45 °C
Heating total input current
°
A
17.2
19.8
A,P
A
18.8
22.9
Electric data
Peak current (LRA)
°
A
84.0
97.0
A,P
A
85.0
100.0
Minimum circuit amperage (MCA)
°,A,P
A
30.0
35.0
Maximum overcurrent permitted by the protec-
tion device (MOP)
°
A
30.0
40.0
A,P
A
35.0
45.0
(1) Data EN 14511:2018; System side water heat exchanger 53.6 °F / 44.6 °F; External air 95.0 °F
(2) Data EN 14511:2018; System side water heat exchanger 104.0 °F / 113.0 °F; External air 45 °F b.s. / 43 °F b.u