23.05 – 6755517_09
15
8
PERFORMANCE SPECIFICATIONS
ANL (°)
Size
100
150
Cooling performance 54.0 °F / 44.1 °F (1)
Cooling capacity
ton
6.57
8.16
Input power
kW
8.24
9.48
Cooling total input current
A
17.0
20.0
EER
BTU/(Wh)
2.80
3.03
IPLV
BTU/(Wh)
4.80
5.19
Water flow rate system side
gpm
15.72
19.52
Pressure drop system side
ftH
2
O
10.04
10.04
Heating performance 104 °F / 113 °F (2)
Heating capacity
BTU/h
94,755
111,850
Input power
kW
8.29
9.57
Heating total input current
A
17.0
20.0
COP
kW/kW
3.350
3.430
Water flow rate system side
gpm
19.11
22.56
Pressure drop system side
ftH
2
O
14.72
12.04
(1) Data: System side water heat exchanger 54.0 °F / 44.1 °F; External air 95 °F
(2) Data: System side water heat exchanger 104 °F / 113 °F; External air 44.6 °F
ANL - (A)
Size
100
150
Cooling performance 54.0 °F / 44.1 °F (1)
Cooling capacity
ton
6.57
8.16
Input power
kW
8.72
10.34
Cooling total input current
A
18.0
21.0
EER
BTU/(Wh)
2.65
2.77
IPLV
BTU/(Wh)
-
-
Water flow rate system side
gpm
15.72
19.52
Useful head system side
ftH
2
O
33.8
44.2
Heating performance 104 °F / 113 °F (2)
Heating capacity
BTU/h
94,755
111,850
Input power
kW
8.80
10.48
Heating total input current
A
18.0
21.0
COP
kW/kW
3.150
3.130
Water flow rate system side
gpm
19.11
22.56
Useful head system side
ftH
2
O
24.1
34.5
(1) Data: System side water heat exchanger 54.0 °F / 44.1 °F; External air 95 °F
(2) Data: System side water heat exchanger 104 °F / 113 °F; External air 44.6 °F
ANL - (P)
Size
100
150
Cooling performance 54.0 °F / 44.1 °F (1)
Cooling capacity
ton
6.57
8.16
Input power
kW
8.72
10.34
Cooling total input current
A
18.0
21.0
EER
BTU/(Wh)
2.65
2.77
IPLV
BTU/(Wh)
-
-
Water flow rate system side
gpm
15.72
19.52
Useful head system side
ftH
2
O
33.8
44.2
Heating performance 104 °F / 113 °F (2)
Heating capacity
BTU/h
94,755
111,850
Input power
kW
8.80
10.48
Heating total input current
A
18.0
21.0
COP
kW/kW
3.150
3.130
Water flow rate system side
gpm
19.11
22.56
Useful head system side
ftH
2
O
24.1
34.5
(1) Data: System side water heat exchanger 54.0 °F / 44.1 °F; External air 95 °F
(2) Data: System side water heat exchanger 104 °F / 113 °F; External air 44.6 °F
8.1 ENERGY DATA
Size
100
150
Part load IPLV
100 %
°,A,P
BTU/(Wh)
4.80
5.19