18 MINIMUM TECHNICAL SPACES
For all units, it is fundamental to respect the minimum distances in order to guar-
antee optimal ventilation to the finned heat exchanger coils to avoid the following:
— The generation of hazardous atmospheres in the case of refrigerant gas leaks;
— Return of hot air;
— Insufficient air flow to the finned heat exchanger coils.
Each side of the unit must have space to allow all routine and extraor-
dinary maintenance to be performed.
The air suction inlet and the vertical air exhaust must not be obstruct-
ed.
The following images indicate the minimum required space:
SINGLE INSTALLATION
A1
C1
B2
C2
B1
* Minimum technical space, to be ensured in order for the chiller to work
properly and for possible maintenance.
The drawings are provided solely as examples.
VERSION A
Size
100
150
Fan
Number
°,A,P
no.
2
2
Minimum technical spaces
A1
°,A,P
in
118.1
118.1
B1
°,A,P
in
31.5
31.5
B2
°,A,P
in
43.3
43.3
C1
°,A,P
in
31.5
31.5
C2
°,A,P
in
31.5
31.5
MULTIPLE INSTALLATION
The minimum distances indicated above guarantee unit operation in the majority
of applications. There are however specific situations that involve the installation
of multiple units:
A
91 in
B
59 in
A
B