31 / 36
TF6400_A
Aereco S.A.
DXA 230
Standard code
DXA1240
DXA1247
Ecodesign
Label (EU Ecodesign Directive)
A+ (with 2 IAQ sensors)
Airflow characteristics
Max. airflow
m
3
/h
230
Other nominal airflows
m
3
/h
80 / 140 / 200
Pressure at exhaust
Pa
60
Airflow compensation (filter clogging)
automatic
Airflow balance (supply and exhaust)
automatic
Acoustics
Sound power level Lw @ 161 m
3
/h, 50 Pa
dB(A)
52
Certifications
CE
Electrics
Power supply
230 VAC, 50 Hz
Motor type
EC (x2)
Power consumption @ 161 m
3
/h @50 Pa
W
36,5
Power consumption @ 230 m
3
/h @50 Pa
W
92,0
Sensors connections
RJ12
Demand control
Compatible versions of DX System
Premium / Excellence
Min - Max Number of sensors for modulation at supply
1 - 5
Min - Max Number of sensors for modulation at exhaust
1 - 5
Sensors type at supply
presence / C0
2
Exhaust units type
humidity / presence / switch / C0
2
/ VOC
Characteristics
Exchanger
polystyrene / counter flow type / 93% efficiency
Filters
on supply air: 2 x F7 / on exhaust air: 1 x G4
Weight
kg
23
Colour
white
Material (main)
expanded polypropylene (EPP) covered by a white galvanized metal sheet
Dimensions
mm
with duct connectors: 1428 x 552 x 545 without duct connectors: 1188 x 552 x 545
Installation
Max. number of main rooms
6
Max. number of technical rooms
5
Connections
2 x (2 x ø160 mm)
Installation
vertical only, to the wall / 2 x 4 points of attachment
Other functions
Interface
2,8” colour touch screen interface / can be built-in or fixed separately
Bypass
controlled by outdoor temperature / also used for free-cooling
Preheating (optional)
with resistance in fresh air ductwork from outside
Condensation management
condensate pump
exhaust through siphon
Temperature of use
Installation room
frost free: +5°C < T°< +50°C
Incoming outdoor fresh air or Extract
-5°C < T° < +50°C without preheating -26°C < T° < +50°C with preheating
Summary of Contents for DXA 230 PREMIUM