19 / 36
TF6400_A
Aereco S.A.
4.2. ELECTRICAL CONNECTION OF THE DEFROSTING
N - P
1 200 W
L1 - P
1 200 W
A1 +
A2 -
Defrosting unit
230 VAC 3 x 1.5 mm²
To circuit breaker 10 A
0.5 mm²
0.5 mm²
DXA Unit
+
-
Details of DXA Unit and defrosting connection
The defrosting has an individual supply in 230 VAC, 50/60 Hz, single-phase via a flexible cable
having a cross-sectional area of at least 1.5 mm². The control is connected via a 2 wire cable
having a cross sectional area of at least 0.5 mm² and a maximal length of 10 meters.
The electrical connection must be made by a professional and comply with the standards in force
in the country of installation.
Plan a contact separation device having an opening distance of at least 3 mm on each pole.
Note:
there is no alarm in the defrosting provided by Aereco.
Details of condensate pump electrical connections
4.3. ELECTRICAL CONNECTION OF THE CONDENSATE PUMP FOR DXA 1247
THE DXA1247 is provided with a built in siphon. It is still possible to connect a condensate pump
after the siphon. The diagram below displays the electrical connections.
Dry contact alarm connections.
The alarm is connected via a 2 wire cable having a cross sectional area of at least 0.5 mm² and a
maximal length of 10 meters.
DXA Unit
+
-
230VAC 3x1.5mm²
To circuit breaker 2A
L (Brown), N(Blue) 230V 0.5mm²
Grey, black
L
N
GND
230VAC blue 1.5mm²
230VAC GND 1.5mm²
230VAC Brown 1.5mm²