Disassembling the Boiler for Maintenance
– Continued
6. Remove the red hoses (quantity depends on model) from bottom side of manifold (Figure 7-
10), then lift entire manifold from the unit.
Figure 7-10: Removing Red Hoses and Manifold from Unit (Step 6)
Figure 7-11: Removing Gas Valve Connector from All Gas Valves (Step 7)
7. On each gas valve, unscrew the Gas Valve Connector with a Phillips head screwdriver.
Remove connector (Figure 7-11) from the side of each gas valve.
Air Intake
Manifold
Remove Red
Hoses from
under Manifold
Lift out manifold after
removing red hoses.
Remove Connector
Retention Screw
Gas Valve
Connector
(remove from